- Asked 2/20
- 2074 Bhadra · 10 marks
Peak load, load factor and energy from load pattern
Short answer
Class peaks: A 10.0 kW, B 2.81 kW, C 3.81 kW. Contribution factors: 1.0, 0.5, 0.1. Transformer peak 11.79 kW, annual load factor 0.47, annual energy sales 48,720 kWh.
The consumer data for particular distribution transformer for a specified year is as shown as follows.
Table-1:
| Consumer class | Class A | Class B | Class C |
|---|---|---|---|
| Consumer number | 80 | 30 | 40 |
| Monthly energy consumption | 30 kWh | 22 kWh | 25 kWh |
| No. of effective days per month | 30 | 24 | 26 |
| Coincidence factor | 1 | 0.9 | 0.95 |
| Power factor | 0.9 | 0.8 | 0.85 |
| Load pattern | Table 2 | Table 2 | Table 2 |
Table-2 (load pattern):
| Time (hrs.) | 0:00-6:00 | 6:00-10:00 | 10:00-14:00 | 14:00-18:00 | 18:00-21:00 | 21:00-24:00 |
|---|---|---|---|---|---|---|
| Class A | 0.1 | 0.4 | 0.2 | 0.2 | 1 | 0.4 |
| Class B | 0.1 | 0.1 | 0.5 | 1 | 0.5 | 0.1 |
| Class C | 0.1 | 0.1 | 1 | 1 | 0.1 | 0.1 |
Determine the following. For each class of consumer: i. peak load ii. Load factor (daily and annual) iii. Contribution factor iv. Annual energy sell. For distribution transformer (Neglect LT losses): i. peak load ii. Load factor iii. Annual energy sells.
The load pattern (Table 2) gives the load of each class in per unit of its peak. From it we find the equivalent full-load hours per day, then the peak from the daily energy.
Method:
Equivalent hours from load pattern
- Class A: h
- Class B: h
- Class C: h
For each consumer class
| Quantity | Class A | Class B | Class C |
|---|---|---|---|
| Daily energy (kWh) | 30/30 = 1.000 | 22/24 = 0.9167 | 25/26 = 0.9615 |
| Individual peak (kW) | 1/8 = 0.125 | 0.9167/8.8 = 0.1042 | 0.9615/9.6 = 0.1002 |
| (i) Class peak (kW) | 80×0.125×1 = 10.00 | 30×0.1042×0.9 = 2.81 | 40×0.1002×0.95 = 3.81 |
| (ii) Daily LF | 8/24 = 0.333 | 8.8/24 = 0.367 | 9.6/24 = 0.400 |
| (ii) Annual LF | 360/(0.125×8760) = 0.329 | 264/(0.1042×8760) = 0.289 | 300/(0.1002×8760) = 0.342 |
| (iv) Annual energy (kWh) | 80×30×12 = 28,800 | 30×22×12 = 7,920 | 40×25×12 = 12,000 |
The annual LF is lower than the daily LF for B and C because they consume only on effective days.
Transformer load curve (kW) = class peak × p.u. pattern
| Time | A | B | C | Total |
|---|---|---|---|---|
| 0–6 | 1.00 | 0.28 | 0.38 | 1.66 |
| 6–10 | 4.00 | 0.28 | 0.38 | 4.66 |
| 10–14 | 2.00 | 1.41 | 3.81 | 7.21 |
| 14–18 | 2.00 | 2.81 | 3.81 | 8.62 |
| 18–21 | 10.00 | 1.41 | 0.38 | 11.79 |
| 21–24 | 4.00 | 0.28 | 0.38 | 4.66 |
The transformer peak occurs at 18:00–21:00.
(iii) Contribution factor of each class
- Class A:
- Class B:
- Class C:
For the distribution transformer
- Peak load: kW. With reactive power kVAR, kVA.
- Annual energy sales (LT losses neglected): kWh.
- Load factor:
Answer: Transformer peak ≈ 11.79 kW (13.29 kVA), annual LF ≈ 0.47, annual energy sales = 48,720 kWh. Class contribution factors are 1.0, 0.5 and 0.1.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load (commercial 30 days) · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load with population growth · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, incremental growth rate · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, 4% growth, 60% coverage · Transmission and Distribution System Design, chapter 6 · asked 7×
- Monthly energy loss of 50 kVA transformer · Transmission and Distribution System Design, chapter 7
- Substation capacity and diversity factor from load pattern · Industrial Power Distribution and Illumination, chapter 1
- World energy resources and consumption pattern · Energy Resources, chapter 8
All Transmission and Distribution System Design chapter 6 questions →