5th year peak load, incremental growth rate

Short answer

Apply consumption growth multiplier (1.05×1.06×1.07×1.08×1.09=1.4019) and population multiplier (1.02^5=1.1041) with 70% coverage to get 5th-year consumers and monthly energy. Individual peak = (daily kWh)/(24×LF). Sum CF×N×P_ind yields peak demand ≈20.5 kW.

From the initial survey of a particular load center, the following consumer data has been obtained.

Consumer classPotential consumerAvg. monthly consumptionNo. of effective days/month5th year contribution factor to peak5th year load factor
Domestic10030 kWh301.00.25
Commercial2030 kWh300.50.30
Non-commercial5020 kWh200.10.25

Determine the 5th year peak load of load center in kW. Data for load forecast (for all consumer classes): Load growth factor: 5% for first year and an increment of 1% from 2nd year. Population growth factor: 2% each year. Percentage coverage factor: 70% by 5th year.

The 5th year peak is found by projecting consumer numbers and consumption, converting daily energy to individual peak with the load factor, and combining class peaks using contribution factors.

Growth multipliers

Consumption growth: 5% in year 1, increasing by 1% each year (6%, 7%, 8%, 9%):

Gc=1.05×1.06×1.07×1.08×1.09=1.40194Gp=(1.02)5=1.10408\begin{aligned} G_c &= 1.05 \times 1.06 \times 1.07 \times 1.08 \times 1.09 = 1.40194 \\ G_p &= (1.02)^5 = 1.10408 \end{aligned}

Formulae

N5=N0×Gp×coverageE5=E0×GcPind=E5/effective days24×LFPLC=∑CF×N5×Pind\begin{aligned} N_5 &= N_0 \times G_p \times \text{coverage} \\ E_5 &= E_0 \times G_c \\ P_{ind} &= \frac{E_5 / \text{effective days}}{24 \times LF} \\ P_{LC} &= \sum CF \times N_5 \times P_{ind} \end{aligned}

Number of consumers (5th year)

ClassN0N_0N5=N0×1.10408×0.7N_5 = N_0 \times 1.10408 \times 0.7
Domestic10077.29
Commercial2015.46
Non-commercial5038.64

Consumption and individual peak

ClassE5E_5 (kWh/month)Daily kWhLFPindP_{ind} (kW)
Domestic30 × 1.40194 = 42.05842.058/30 = 1.40190.250.23366
Commercial42.05842.058/30 = 1.40190.300.19471
Non-commercial20 × 1.40194 = 28.03928.039/20 = 1.40190.250.23366

Example (commercial): Pind=1.401924×0.30=0.19471P_{ind} = \dfrac{1.4019}{24 \times 0.30} = 0.19471 kW.

Contribution to load centre peak

ClassClass peak (kW)CFContribution (kW)
Domestic77.29 × 0.23366 = 18.0581.018.058
Commercial15.46 × 0.19471 = 3.0100.51.505
Non-commercial38.64 × 0.23366 = 9.0290.10.903
Total20.47

Answer: 5th year peak load of the load centre ≈ 20.5 kW (20.47 kW).