5th year peak load (commercial 30 days)
Short answer
Grow each class's monthly consumption by (1.05)⁵ = 1.27628, apply 70% coverage to consumer numbers, divide daily energy by (24 × LF) for individual peak, then sum class peaks weighted by contribution factors. The 5th year peak load is approximately 16.88 kW.
From the initial survey of a particular load center, the following consumer data has been obtained.
| Consumer class | Potential consumer no. | Avg. monthly consumption | No. of effective days/month | 5th year contribution factor to peak | 5th year load factor |
|---|---|---|---|---|---|
| Domestic | 100 | 30 kWhr | 30 | 1.0 | 0.25 |
| Commercial | 20 | 30 kWhr | 30 | 0.5 | 0.30 |
| Non-commercial | 50 | 20 kWhr | 20 | 0.1 | 0.25 |
Assuming consumption growth factors of 5% in each year and electrification coverage factor by 5th year is 70% for all consumer classes determine the 5th year peak load of the load center in kW.
The 5th year peak of the load centre is found by growing each class's consumption to the 5th year, applying the coverage factor to the consumer number, converting daily energy to individual peak using the 5th year load factor, and adding class peaks weighted by their contribution factors.
Assumption: no population growth is given, so the number of potential consumers stays the same; growth is applied for years.
Formulae
Step 1: Consumption growth multiplier
Step 2: Effective number of consumers
| Class | ||
|---|---|---|
| Domestic | 100 | 70 |
| Commercial | 20 | 14 |
| Non-commercial | 50 | 35 |
Step 3: Consumption and individual peak demand
| Class | (kWh/month) | (kWh) | (kW) | |
|---|---|---|---|---|
| Domestic | 30 × 1.27628 = 38.288 | 38.288/30 = 1.2763 | 0.25 | 0.21271 |
| Commercial | 38.288 | 38.288/30 = 1.2763 | 0.30 | 0.17726 |
| Non-commercial | 20 × 1.27628 = 25.526 | 25.526/20 = 1.2763 | 0.25 | 0.21271 |
Sample calculation (domestic):
Step 4: Class peak and contribution to load centre peak
| Class | Class peak (kW) | CF | Contribution (kW) |
|---|---|---|---|
| Domestic | 70 × 0.21271 = 14.890 | 1.0 | 14.890 |
| Commercial | 14 × 0.17726 = 2.482 | 0.5 | 1.241 |
| Non-commercial | 35 × 0.21271 = 7.445 | 0.1 | 0.745 |
| Total | 24.817 | 16.875 |
Step 5: Load centre peak
Note that the plain sum of class peaks (24.82 kW) would overestimate the demand by about 47%, because commercial and non-commercial loads peak at other hours.
Answer: 5th year peak load of the load centre ≈ 16.88 kW.
For transformer selection, this would be converted to kVA (e.g. at 0.85 p.f., kVA), plus a loss allowance, so a standard 25 kVA transformer would be suitable.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 5th year peak load, 4% growth, 60% coverage · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load with population growth · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, incremental growth rate · Transmission and Distribution System Design, chapter 6 · asked 7×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- Peak load, load factor and energy from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
All Transmission and Distribution System Design chapter 6 questions →