- Asked 7/20
- 2077 Chaitra · 10 marks
5th year peak load with population growth
Short answer
With 7 years of 1.8% population and 5% consumption growth, 70% coverage, individual peak 0.2345 kW, and contribution factors 1.0, 0.5, 0.1, the 5th-year peak load is 21.4 kW.
From the initial survey of particular load center, the following consumer data has been obtained.
| Consumer class | Potential consumer | Avg. monthly consumption | No. of effective days/month | 5th year contribution factor to peak | 5th year load factor |
|---|---|---|---|---|---|
| Domestic | 100 | 30 kWh | 30 | 1.0 | 0.25 |
| Commercial | 20 | 30 kWh | 25 | 0.5 | 0.30 |
| Non-commercial | 50 | 20 kWh | 20 | 0.1 | 0.25 |
Assuming population growth factor of 1.8%, consumption growth factors of 5% in each year for each class and electrification coverage factor by 5th year is 70% for all consumers classes, determine 5th year peak load of the load center in kW. Also, project implementation period be 2 years.
The load centre peak is found by projecting the number of consumers and their consumption to the 5th year, converting energy to peak using the load factor, and combining the class peaks with their contribution factors.
Assumptions: The 5th year is counted after project completion, so with a 2-year implementation period the growth period from the survey is years for both population and consumption.
Formulae
Growth multipliers
Number of consumers in 5th year
| Class | ||
|---|---|---|
| Domestic | 100 | 79.31 |
| Commercial | 20 | 15.86 |
| Non-commercial | 50 | 39.66 |
Consumption and individual peak
| Class | (kWh/month) | Daily (kWh) | LF | (kW) |
|---|---|---|---|---|
| Domestic | 30 × 1.4071 = 42.213 | 42.213/30 = 1.4071 | 0.25 | 0.23452 |
| Commercial | 42.213 | 42.213/25 = 1.6885 | 0.30 | 0.23452 |
| Non-commercial | 20 × 1.4071 = 28.142 | 28.142/20 = 1.4071 | 0.25 | 0.23452 |
Example (domestic): kW.
Class peak and contribution to load centre peak
| Class | Class peak (kW) | CF | Contribution (kW) |
|---|---|---|---|
| Domestic | 79.31 × 0.23452 = 18.600 | 1.0 | 18.600 |
| Commercial | 15.86 × 0.23452 = 3.720 | 0.5 | 1.860 |
| Non-commercial | 39.66 × 0.23452 = 9.300 | 0.1 | 0.930 |
| Total | 21.39 |
Answer: 5th year peak load of the load centre ≈ 21.4 kW.
(If the implementation period were ignored, i.e. , the result would be lower; the 2-year period is included because consumers keep growing while the project is being built.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 5th year peak load (commercial 30 days) · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, 4% growth, 60% coverage · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, incremental growth rate · Transmission and Distribution System Design, chapter 6 · asked 7×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- Peak load, load factor and energy from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
All Transmission and Distribution System Design chapter 6 questions →