- Asked 7/20
- 2067 Mangsir (old course) · 12 marks
5th year peak load, 4% growth, 60% coverage
Short answer
Project consumption with (1.04)⁵ = 1.21665, apply 60% coverage to consumer numbers, compute individual peak as daily energy ÷ (24 × LF), and sum contributions. The 5th year peak load of the load centre is approximately 27.26 kW.
From the initial survey of a particular load center the following consumer data has been obtained:
| Consumer class | Potential consumer no. | Avg. monthly consumption | No. of effective days/month | 5th year contribution factor to peak | 5th year load factor |
|---|---|---|---|---|---|
| Domestic | 200 | 30 kWhr | 30 | 1.0 | 0.25 |
| Commercial | 50 | 30 kWhr | 30 | 0.5 | 0.30 |
| Non-commercial | 40 | 20 kWhr | 25 | 0.1 | 0.25 |
Assuming a uniform consumption growth factors of 4% in each year and electrification coverage factor by 5th year is 60% for all consumer classes determine the 5th year peak load of the load center in kW.
The method: project each class's consumption to the 5th year, apply the coverage factor to the consumer numbers, convert daily energy to individual peak demand using the load factor, then combine the class peaks using their contribution factors.
Assumption: no population growth is given, so potential consumer numbers stay constant; consumption grows for years.
Formulae
Step 1: Growth multiplier
Step 2: Connected consumers in 5th year (60% coverage)
| Class | ||
|---|---|---|
| Domestic | 200 | 120 |
| Commercial | 50 | 30 |
| Non-commercial | 40 | 24 |
Step 3: Consumption and individual peak
| Class | (kWh/month) | Daily kWh | (kW) | |
|---|---|---|---|---|
| Domestic | 30 × 1.21665 = 36.500 | 36.500/30 = 1.2167 | 0.25 | 0.20278 |
| Commercial | 36.500 | 36.500/30 = 1.2167 | 0.30 | 0.16898 |
| Non-commercial | 20 × 1.21665 = 24.333 | 24.333/25 = 0.9733 | 0.25 | 0.16222 |
Sample (non-commercial):
Step 4: Class peaks and contribution
| Class | Class peak (kW) | CF | Contribution (kW) |
|---|---|---|---|
| Domestic | 120 × 0.20278 = 24.333 | 1.0 | 24.333 |
| Commercial | 30 × 0.16898 = 5.069 | 0.5 | 2.535 |
| Non-commercial | 24 × 0.16222 = 3.893 | 0.1 | 0.389 |
| Total | 33.296 | 27.257 |
Step 5: Load centre peak
The non-coincident sum (33.30 kW) is higher because commercial and non-commercial classes do not peak with the domestic evening peak.
Answer: 5th year peak load of the load centre ≈ 27.26 kW.
At about 0.85 p.f. this is roughly 32 kVA; allowing for losses and later growth, a 50 kVA standard transformer would be selected.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 5th year peak load (commercial 30 days) · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load with population growth · Transmission and Distribution System Design, chapter 6 · asked 7×
- 5th year peak load, incremental growth rate · Transmission and Distribution System Design, chapter 6 · asked 7×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
All Transmission and Distribution System Design chapter 6 questions →