Pitch factor, distribution factor and EMF equation
Short answer
Pitch factor kp = cos(α/2) accounts for emf reduction when coils are short-pitched, which suppresses harmonics. Distribution factor kd = sin(mβ/2)/(m sin(β/2)) arises from distributed coils, giving a more sinusoidal wave. RMS emf per phase: Eph = 4.44 kp kd f Φ T V, where T is turns per phase.
Define the pitch factor and distribution factor and their significance in synchronous machine. Derive the e.m.f equation of an alternator.
Pitch factor (coil span factor),
The pitch factor is the ratio of the emf induced in a short-pitched (chorded) coil to the emf that would be induced in a full-pitched coil.
If the coil is short of full pitch (180° electrical) by an angle , the emfs in the two coil sides are not in phase and add as phasors:
Significance: short pitching slightly reduces the emf () but it eliminates or reduces harmonics (e.g. removes the 5th harmonic, since ), saves copper in end connections and reduces leakage reactance.
Distribution (breadth) factor,
The distribution factor is the ratio of the phasor sum to the arithmetic sum of the emfs of coils distributed in several slots of a phase group.
With slots per pole per phase and slot angle :
Significance: distributing the winding gives a more sinusoidal emf, better use of the core and better cooling; only slightly reduces the emf.
EMF equation of an alternator
Let
- = number of poles, = speed in rpm,
- = flux per pole (Wb), = conductors in series per phase, turns per phase.
In one revolution, each conductor cuts flux in time seconds.
(form factor of a sine wave = 1.11). Including the winding factors for a short-pitched, distributed winding:
For a star-connected machine, line voltage ; for delta, . The product is called the winding factor.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Synchronous generator principle and EMF equation · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Change in emf to raise power factor to unity · Electric Machines II, chapter 1
- Construction of synchronous machine and rotor types · Electric Machines II, chapter 1 · asked 2×
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- EMF equation of an alternator · Electrical Machines, chapter 6
- Swing equation of synchronous machine · Power System Analysis II, chapter 6
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6