Change in emf to raise power factor to unity
Short answer
Initial emf E1 = √((V cosφ+IR)²+(V sinφ+IX)²) = 7082.87 V per phase. At unity pf, current reduces to 240 A (same power). New emf E2 = √((V+IR)²+(IX)²) = 6043.56 V. Percentage change = (6043.56-7082.87)/7082.87×100 = -14.67%.
A 3 phase, star connected alternator with R = 0.4 Ω and X = 6 Ω per phase delivers 300 A at power factor 0.8 to constant frequency 10 kV busbars. If the steam supply is unchanged, find the percentage change in the induced emf necessary to raise the power factor to unity. Ignore the change in losses.
Given: star, , per phase, 300 A at 0.8 pf (taken lagging) on 10 kV constant-frequency bus-bars; steam supply unchanged, so output power is constant.
Initial emf (0.8 pf lagging, 300 A)
New current at unity pf (same power)
New emf
Percentage change
Answer: the induced emf must be reduced by about 14.67% (from 7082.9 V to 6043.6 V per phase) to bring the pf to unity.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Internal emf, no-load emf and regulation · Electric Machines II, chapter 1
- Back emf and new current of 5 kVA motor · Electric Machines II, chapter 2 · asked 3×
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- Balanced circulating current: 10 kV alternator · Switchgear and Protection, chapter 7