Skip to main content

Chapter 7 · 5 hours

HVDC power transmission

IOE past exam questions

Past questions and answers

11 questions set from this chapter, 5 of them more than once. Most asked first.

  • Asked 4 times
  • 2076 Asoj · 8 marks
  • 2075 Chaitra · 8 marks
  • 2071 Chaitra · 8 marks
  • 2069 Chaitra · 8 marks

Why HVDC transmission is preferred over HVAC transmission for transport of large power over long distance? What are the differences between HVAC and HVDC transmission lines? Perform a mathematical comparison between HVAC and HVDC lines.

Answer

HVDC transmission sends bulk power over long distances at high DC voltage, with a rectifier station at the sending end and an inverter station at the receiving end. It is preferred over HVAC for large power over long distances because the saving in line cost and losses exceeds the extra cost of the converter stations.

Why HVDC for large power over long distance

  • Lower line cost: a bipolar DC line needs only 2 conductors instead of 3, smaller towers and narrower right of way. Terminal (converter) cost is high, but beyond the break-even distance (about 500–800 km for overhead lines, 40–80 km for cables) the total cost of DC is lower.
  • No stability limit: AC power P=V1V2Xsin⁡δP = \dfrac{V_1V_2}{X}\sin\delta falls as line reactance grows with length; DC has no reactance or load angle, so power is limited only by thermal rating.
  • No reactive power or charging current: no need for line compensation; voltage stays nearly constant along the line.
  • Lower losses: no skin effect, less corona, fewer conductors.
  • Asynchronous link and fast power control by firing angle.
 Cost
  |                      / AC
  |                    /
  |                  /    _____ DC
  |            _____X-----
  |     _____-    / :
  | DC -        /   :
  |           /     :
  |  AC     /       :
  |       /         :
  |     /           :
  +-----------------:------> km
             break-even distance

Differences between HVAC and HVDC lines

PointHVACHVDC
Conductors3 (3-phase)2 (bipolar), 1 (monopolar)
Stability limitYes, P∝sin⁡δ/XP \propto \sin\delta / XNone
Reactive powerCharging current, needs compensationNone in line
Skin effect / coronaPresent / moreAbsent / less
Terminal costLow (transformers)High (converters, filters)
Line cost per kmHighLow
InterconnectionSynchronous onlyAsynchronous possible
Fault currentHighLimited by converter control
Voltage changeEasy (transformer)Needs converter
HarmonicsLittleConverter harmonics, filters needed

Mathematical comparison

(a) Power transfer. Assumptions: same conductor size and current rating (same rms current II per conductor), same insulation, i.e. the same peak voltage to ground VmV_m; three-phase AC line with 3 conductors; bipolar DC line with 2 conductors at ±Vd\pm V_d, Vd=VmV_d = V_m, Id=II_d = I.

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VdId=2VmI\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_m I\cos\phi \\ P_{dc} &= 2V_d I_d = 2V_m I \end{aligned} PdcPac=2VmI2.121 VmIcos⁡ϕ=0.943cos⁡ϕ\frac{P_{dc}}{P_{ac}} = \frac{2V_m I}{2.121\,V_m I\cos\phi} = \frac{0.943}{\cos\phi}

Per conductor:

Pdc/2Pac/3=VmI0.707 VmIcos⁡ϕ=1.414cos⁡ϕ\frac{P_{dc}/2}{P_{ac}/3} = \frac{V_m I}{0.707\,V_m I\cos\phi} = \frac{1.414}{\cos\phi}

With cos⁡ϕ≈0.943\cos\phi \approx 0.943, a 2-conductor DC line carries the same power as a 3-conductor AC line, and each DC conductor carries about 1.41 times more power at unity pf.

(b) Losses. For the same power and same loss per conductor, total loss is

LossdcLossac=2p3p=23\frac{\text{Loss}_{dc}}{\text{Loss}_{ac}} = \frac{2p}{3p} = \frac{2}{3}

(c) Conductor material. For the same power, voltage and loss, the DC line needs only 0.5cos⁡2ϕ0.5\cos^2\phi times the conductor volume of the AC line (50% at unity pf).

(d) Insulation. AC insulation must withstand the peak 2Vrms\sqrt{2}V_{rms}; DC insulation is set by VdV_d, so for the same working level a DC line needs less insulation.

  • Asked 2 times
  • 2082 Baishakh · 8 marks
  • 2073 Shrawan · 8 marks

Why is HVDC transmission preferred over HVAC transmission for transport of large power over a long distance? What are the advantages of HVDC transmission line compared with HVAC transmission line? Perform a mathematical analysis to compare power transfer capacities of these lines.

Answer

HVDC transmission uses a rectifier at the sending end, a DC line, and an inverter at the receiving end. For large power over long distances it is cheaper and more efficient than HVAC because the line is cheaper and has no stability or reactive-power limits; the high converter cost is recovered beyond the break-even distance.

Why HVDC for large power over long distance

  • Lower line cost: a bipolar DC line needs only 2 conductors instead of 3, smaller towers and narrower right of way. Terminal (converter) cost is high, but beyond the break-even distance (about 500–800 km for overhead lines, 40–80 km for cables) the total cost of DC is lower.
  • No stability limit: AC power P=V1V2Xsin⁡δP = \dfrac{V_1V_2}{X}\sin\delta falls as line reactance grows with length; DC has no reactance or load angle, so power is limited only by thermal rating.
  • No reactive power or charging current: no need for line compensation; voltage stays nearly constant along the line.
  • Lower losses: no skin effect, less corona, fewer conductors.
  • Asynchronous link and fast power control by firing angle.

Advantages of HVDC over HVAC lines

  1. Only 2 conductors (bipolar) or 1 conductor with earth return (monopolar); lighter towers, narrower corridor.
  2. No charging current, so no limit on length of underground or submarine cables.
  3. No skin effect; full conductor area is used.
  4. Less corona loss and radio interference for the same voltage.
  5. Fast and accurate control of power flow by firing angle; can damp oscillations in connected AC systems.
  6. Can link AC systems of different frequencies or not in synchronism (e.g. 50 Hz and 60 Hz).
  7. Does not raise the fault level of the connected AC systems; DC line faults are cleared quickly by converter control.
  8. One pole can continue to work if the other fails (bipolar link) with earth return.

Mathematical comparison of power transfer capacity

Assumptions: same conductor size and current rating (same rms current II per conductor), same insulation, i.e. the same peak voltage to ground VmV_m; three-phase AC line with 3 conductors; bipolar DC line with 2 conductors at ±Vd\pm V_d, Vd=VmV_d = V_m, Id=II_d = I.

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VdId=2VmI\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_m I\cos\phi \\ P_{dc} &= 2V_d I_d = 2V_m I \end{aligned} PdcPac=2VmI2.121 VmIcos⁡ϕ=0.943cos⁡ϕ\frac{P_{dc}}{P_{ac}} = \frac{2V_m I}{2.121\,V_m I\cos\phi} = \frac{0.943}{\cos\phi}

Per conductor:

Pdc/2Pac/3=VmI0.707 VmIcos⁡ϕ=1.414cos⁡ϕ\frac{P_{dc}/2}{P_{ac}/3} = \frac{V_m I}{0.707\,V_m I\cos\phi} = \frac{1.414}{\cos\phi}

Interpretation:

  • At cos⁡ϕ=0.943\cos\phi = 0.943, Pdc=PacP_{dc} = P_{ac}: a DC line with two conductors carries the same power as an AC line with three conductors of the same size and insulation.
  • At unity power factor, Pdc/Pac=0.943P_{dc}/P_{ac} = 0.943, but per conductor the DC line carries 2=1.414\sqrt{2} = 1.414 times more power, because the DC conductor works continuously at the peak voltage VmV_m while the AC conductor's rms voltage is only Vm/2V_m/\sqrt{2}.
  • So for the same power, DC needs one conductor less and its loss is about 2/3 of that of the AC line.
  • Asked 2 times
  • 2080 Bhadra · 8 marks
  • 2080 Baishakh · 8 marks

Why HVDC line is preferred over HVAC line to transport large power over a long distance? Make a mathematical comparison between HVAC and HVDC lines to justify line conductor saving in HVDC line.

Answer

An HVDC line is preferred for large power over long distance because, after the break-even distance, the cheaper DC line (fewer conductors, less insulation, lower losses, no reactive power) outweighs the extra cost of converter stations.

Reasons

  • Lower line cost: a bipolar DC line needs only 2 conductors instead of 3, smaller towers and narrower right of way. Terminal (converter) cost is high, but beyond the break-even distance (about 500–800 km for overhead lines, 40–80 km for cables) the total cost of DC is lower.
  • No stability limit: AC power P=V1V2Xsin⁡δP = \dfrac{V_1V_2}{X}\sin\delta falls as line reactance grows with length; DC has no reactance or load angle, so power is limited only by thermal rating.
  • No reactive power or charging current: no need for line compensation; voltage stays nearly constant along the line.
  • Lower losses: no skin effect, less corona, fewer conductors.
  • Asynchronous link and fast power control by firing angle.

Mathematical comparison: conductor saving

Assumptions: same power PP, same length ll, same peak voltage to ground VmV_m (same insulation), same total loss, same conductor material (resistivity ρ\rho).

AC (3 conductors, area AacA_{ac}) and DC (2 conductors, area AdcA_{dc}):

Iac=P3(Vm/2)cos⁡ϕ,Idc=P2VmLossac=3Iac2ρlAac=2P2ρl3Vm2cos⁡2ϕ AacLossdc=2Idc2ρlAdc=P2ρl2Vm2Adc\begin{aligned} I_{ac} &= \frac{P}{3(V_m/\sqrt{2})\cos\phi}, \qquad I_{dc} = \frac{P}{2V_m} \\ \text{Loss}_{ac} &= 3I_{ac}^2\frac{\rho l}{A_{ac}} = \frac{2P^2\rho l}{3V_m^2\cos^2\phi\,A_{ac}} \\ \text{Loss}_{dc} &= 2I_{dc}^2\frac{\rho l}{A_{dc}} = \frac{P^2\rho l}{2V_m^2A_{dc}} \end{aligned}

Equating the losses:

AdcAac=1/22/(3cos⁡2ϕ)=0.75cos⁡2ϕ\frac{A_{dc}}{A_{ac}} = \frac{1/2}{2/(3\cos^2\phi)} = 0.75\cos^2\phi

Ratio of conductor volume (material):

VoldcVolac=2Adcl3Aacl=23×0.75cos⁡2ϕ=0.5cos⁡2ϕ\frac{\text{Vol}_{dc}}{\text{Vol}_{ac}} = \frac{2A_{dc}l}{3A_{ac}l} = \frac{2}{3}\times 0.75\cos^2\phi = 0.5\cos^2\phi

Result:

Power factor of AC lineAdc/AacA_{dc}/A_{ac}DC conductor material as % of AC
1.00.7550%
0.90.6140.5%
0.80.4832%

At unity power factor, the DC line needs only half the conductor material of an equivalent AC line for the same power, voltage stress and losses; at lower AC power factor the saving is even greater. Fewer and lighter conductors also mean lighter towers and a narrower right of way, which is why HVDC lines are cheaper per km.

  • Asked 2 times
  • 2079 Baishakh · 8 marks
  • 2073 Chaitra · 8 marks

Justify that the total power loss of HVDC transmission line is only 2/3th of total power loss in HVAC transmission line. Make assumption that the power loss per conductor is same for both lines and also the transmission capacity of both lines are same.

Answer

The claim compares a three-phase HVAC line (3 conductors) with a bipolar HVDC line (2 conductors) of the same power capacity, assuming each conductor has the same loss.

Step 1: Show that both lines carry the same power

Let both lines use the same conductors (same rms current II, resistance RR per conductor) and the same insulation (same peak voltage to earth VmV_m). For DC: Vd=VmV_d = V_m, Id=II_d = I.

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VdId=2VmI\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_mI\cos\phi \\ P_{dc} &= 2V_dI_d = 2V_mI \end{aligned}

Equating, Pdc=PacP_{dc} = P_{ac} when cos⁡ϕ=223=0.943\cos\phi = \dfrac{2\sqrt{2}}{3} = 0.943, which is a typical operating power factor. So a 2-conductor DC line has practically the same capacity as a 3-conductor AC line.

Step 2: Loss per conductor

Since both carry the same current II (rms for AC, DC value for DC) through the same resistance RR:

pac=I2R=pdc=pp_{ac} = I^2R = p_{dc} = p

(This is the given assumption.)

Step 3: Total losses

Lossac=3I2R=3pLossdc=2I2R=2p\begin{aligned} \text{Loss}_{ac} &= 3I^2R = 3p \\ \text{Loss}_{dc} &= 2I^2R = 2p \end{aligned} LossdcLossac=2p3p=23\frac{\text{Loss}_{dc}}{\text{Loss}_{ac}} = \frac{2p}{3p} = \frac{2}{3}

Hence the total power loss of the HVDC line is only 2/3 of that of the HVAC line of the same capacity.

 HVAC:  ===== a  (loss p)      HVDC: ===== +Vd (loss p)
        ===== b  (loss p)            ===== -Vd (loss p)
        ===== c  (loss p)
 Total: 3p                    Total: 2p

Further points

  • Efficiency of DC is also higher because there is no skin effect (AC resistance > DC resistance) and corona loss is lower.
  • No reactive (charging) current flows in a DC line, so the full current rating carries real power.
  • Converter station losses (about 0.5–1% per station) must be added, which is why HVDC pays off only for long distances.
  • Asked 2 times
  • 2076 Chaitra · 8 marks
  • 2072 Kartik · 8 marks

In which circumstance, HVDC transmission line has advantages over the HVAC transmission line? Prove that a HVDC line with two conductors can transmit same amount of power as transmitted by HVAC line with three conductors of same size. What type of power electronic converter is used in HVDC line and why?

Answer

HVDC has advantages over HVAC when large power is to be sent over a long distance (beyond the break-even distance), and in some special cases.

Circumstances favouring HVDC

  1. Bulk power over long overhead lines (beyond about 500–800 km).
  2. Submarine or underground cables longer than about 40–80 km, where AC charging current would use up the cable rating.
  3. Linking two AC systems of different frequency, or not synchronised (asynchronous tie).
  4. Where fast power-flow control or stability support is needed, and to avoid raising fault levels.
  5. Where right of way is limited (fewer conductors, smaller towers).

Proof: 2 DC conductors carry the same power as 3 AC conductors

Assumptions: all conductors same size (same current II), same insulation level (peak voltage to earth VmV_m).

AC three-phase line, phase voltage rms Vm/2V_m/\sqrt{2}:

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕP_{ac} = 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_mI\cos\phi

Bipolar DC line, ±Vd\pm V_d with Vd=VmV_d = V_m, Id=II_d = I:

Pdc=2VdId=2VmIP_{dc} = 2V_dI_d = 2V_mI

Ratio:

PdcPac=22.121cos⁡ϕ=0.943cos⁡ϕ\frac{P_{dc}}{P_{ac}} = \frac{2}{2.121\cos\phi} = \frac{0.943}{\cos\phi}

For the usual power factor cos⁡ϕ=0.943\cos\phi = 0.943 (or close to it), Pdc=PacP_{dc} = P_{ac}. So a 2-conductor HVDC line transmits the same power as a 3-conductor HVAC line with the same conductor size and insulation. In addition, its line loss is only 2I2R2I^2R against 3I2R3I^2R, i.e. 2/3.

Converter used in HVDC and why

  • Line-commutated, fully controlled three-phase thyristor bridge converters, usually connected as 12-pulse units (two 6-pulse bridges fed by Y-Y and Y-Δ transformers).
  • The same bridge works as a rectifier (α<90°\alpha < 90°) at the sending end and an inverter (α>90°\alpha > 90°) at the receiving end, so power can be reversed by changing firing angles.
  • Thyristors are available in very high voltage and current ratings and can be series-connected into valves; they use natural commutation (no extra commutation circuit).
  • 12-pulse operation cancels the 5th and 7th harmonics, reducing filter size.
  • Newer schemes also use voltage source converters (VSC) with IGBTs, which allow independent reactive power control and connection to weak networks.
  • 2081 Bhadra · 2+2 marks

What are the advantages HVDC transmission line over the HVAC transmission line? Why negative line is used for transmission in homopolar HVDC?

Answer

Advantages of HVDC over HVAC

  • Only 2 conductors (bipolar) or 1 (monopolar with earth return): cheaper towers and line.
  • No stability limit, so power capacity does not fall with line length.
  • No reactive power and charging current; any cable length is possible.
  • No skin effect; lower corona and line losses (about 2/3 of AC for the same power).
  • Can connect asynchronous AC systems or systems of different frequencies.
  • Fast power-flow control by firing angle; does not add to AC fault level.

Why negative polarity is used in homopolar HVDC

A homopolar link has two or more conductors of the same polarity with earth return. Negative polarity is chosen because:

  • Corona loss is lower with a negative conductor than with a positive one at the same voltage.
  • Radio and audible interference produced by corona is much less for negative polarity.
  • Since all conductors have the same polarity, choosing negative gives these benefits on every conductor.
  Rect ===(-Vd)=== Inv
  Rect ===(-Vd)=== Inv
   |               |
  earth ......... earth (return)
  • 2078 Bhadra · 8 marks

Compare AC transmission over HVDC transmission. Justify that total power loss in HVDC is only 2/3th of total power loss in HVAC transmission lines.

Answer

HVAC transmission sends power as three-phase AC through transformers; HVDC converts AC to DC at the sending end (rectifier), transmits DC, and converts back to AC (inverter). Each is best in a different range.

Comparison of AC and DC transmission

PointHVACHVDC
Conductors3 (3-phase)2 (bipolar), 1 (monopolar)
Stability limitYes, P∝sin⁡δ/XP \propto \sin\delta / XNone
Reactive powerCharging current, needs compensationNone in line
Skin effect / coronaPresent / moreAbsent / less
Terminal costLow (transformers)High (converters, filters)
Line cost per kmHighLow
InterconnectionSynchronous onlyAsynchronous possible
Fault currentHighLimited by converter control
Voltage changeEasy (transformer)Needs converter
HarmonicsLittleConverter harmonics, filters needed

AC is cheaper for short and medium distances because terminals are simple; DC is cheaper for long distances (beyond the break-even distance) and for long cables.

Justification of the 2/3 loss

Assumptions: same power capacity, same conductor size and current II, same loss per conductor p=I2Rp = I^2R, same insulation (peak voltage to earth VmV_m, with Vd=VmV_d = V_m).

Same capacity:

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VmI\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_mI\cos\phi \\ P_{dc} &= 2V_mI \end{aligned}

These are equal for cos⁡ϕ=0.943\cos\phi = 0.943, so a 2-conductor bipolar DC line has the same capacity as a 3-conductor AC line.

Total losses:

LossdcLossac=2I2R3I2R=2p3p=23\frac{\text{Loss}_{dc}}{\text{Loss}_{ac}} = \frac{2I^2R}{3I^2R} = \frac{2p}{3p} = \frac{2}{3}

Hence the HVDC line loss is only 2/3 of the HVAC line loss for the same power. In practice the saving is a little more, because the AC resistance is higher due to skin effect and AC lines have more corona loss.

  • 2075 Asoj · 8 marks

With mathematical aid, explain how full converters can be used for reverse power flow in bipolar link of HVDC transmission.

Answer

In a bipolar HVDC link, each end has two fully controlled (thyristor) converters in series with the mid-point earthed; one pole is at +Vd+V_d and the other at −Vd-V_d. Because a full converter can work as a rectifier (α<90°\alpha < 90°) or as an inverter (α>90°\alpha > 90°), power flow is reversed simply by changing the firing angles at both ends; the current direction cannot change, so the pole voltages reverse.

Bipolar link

  Station 1                    Station 2
 [Conv 1P] +Vd ======Id=====> [Conv 2P]
     |                            |
   earth                        earth
     |                            |
 [Conv 1N] -Vd <=====Id====== [Conv 2N]

Each pole forms a link like the following (one pole shown):

   AC sys 1                         AC sys 2
     |   Conv 1      R, Ld      Conv 2   |
     +--[3-ph full]--+--/\/\--+--[3-ph full]--+
        bridge  Vd1 (+)  Id -> (+) Vd2'  bridge
                 |               |
                 +---------------+
 Vd1 = Vdo cos a1     Vd2' = -Vdo cos a2

Mathematical analysis

Let both converters have the same no-load voltage Vdo=32VLπV_{do} = \dfrac{3\sqrt{2}V_L}{\pi} and the line resistance be RR. Converter 1 gives Vd1=Vdocos⁡α1V_{d1} = V_{do}\cos\alpha_1. Converter 2 is connected in opposition, so its terminal voltage seen by the line is Vd2′=−Vdocos⁡α2V_{d2}' = -V_{do}\cos\alpha_2. Thyristors allow current IdI_d in one direction only:

Id=Vd1−Vd2′R=Vdo(cos⁡α1+cos⁡α2)R≥0I_d = \frac{V_{d1} - V_{d2}'}{R} = \frac{V_{do}(\cos\alpha_1 + \cos\alpha_2)}{R} \ge 0

Power sent by converter 1 and received by converter 2:

P1=Vdocos⁡α1 Id,P2=−Vdocos⁡α2 Id,P1−P2=Id2RP_1 = V_{do}\cos\alpha_1\,I_d, \qquad P_2 = -V_{do}\cos\alpha_2\,I_d, \qquad P_1 - P_2 = I_d^2R

Case 1: power from system 1 to system 2.

  • α1<90°\alpha_1 < 90°: converter 1 is a rectifier (Vd1>0V_{d1} > 0, P1>0P_1 > 0).
  • α2>90°\alpha_2 > 90°: converter 2 is an inverter (cos⁡α2<0\cos\alpha_2 < 0, P2>0P_2 > 0 delivered to system 2).
  • Line voltage is positive at the top conductor.

Case 2: power from system 2 to system 1 (reversal).

  • Make α1>90°\alpha_1 > 90°: converter 1 becomes an inverter (Vd1<0V_{d1} < 0).
  • Make α2<90°\alpha_2 < 90°: converter 2 becomes a rectifier.
  • The current direction stays the same; only the polarity of the DC line voltage reverses, so P=VdIdP = V_dI_d changes sign.

Condition for current flow in both cases:

cos⁡α1+cos⁡α2>0  ⇒  cos⁡α1>cos⁡(180°−α2)  ⇒  α1+α2<180°\cos\alpha_1 + \cos\alpha_2 > 0 \;\Rightarrow\; \cos\alpha_1 > \cos(180° - \alpha_2) \;\Rightarrow\; \alpha_1 + \alpha_2 < 180°

For a line of small resistance, IdRI_dR is small, so

α1+α2≈180°,i.e. α2≈180°−α1\alpha_1 + \alpha_2 \approx 180°, \quad \text{i.e. } \alpha_2 \approx 180° - \alpha_1

The magnitude of IdI_d (and power) is set by how much α1+α2\alpha_1 + \alpha_2 is less than 180°180°; the direction of power is set by which converter has α<90°\alpha < 90°.

Modeα1\alpha_1α2\alpha_2Line polarityPower
Normal<90°< 90° (rectifier)>90°> 90° (inverter)+1 → 2
Reversed>90°> 90° (inverter)<90°< 90° (rectifier)−2 → 1

In the bipolar link

  • Both poles are controlled together. In normal mode the upper pole is +Vd+V_d and the lower −Vd-V_d; on reversal both polarities swap (upper becomes −Vd-V_d, lower +Vd+V_d), while the pole currents keep their directions.
  • Total power P=2VdIdP = 2V_dI_d reverses with no mechanical switching.
  • In practice, the rectifier controls current (constant current) and the inverter controls extinction angle (γ\gamma control); reversal is done by ramping current to a low value, reversing the voltage by changing α\alpha, then raising current.
  • 2073 Shrawan · 8 marks

With the help of suitable circuit diagram, describe the operation of reversible power flow on DC line.

Answer

In a DC (HVDC) line with thyristor converters at both ends, the direction of current cannot reverse because thyristors conduct only one way. Power flow is reversed by reversing the polarity of the DC voltage, which is done by changing the firing angles: the rectifier becomes an inverter and the inverter becomes a rectifier.

Circuit

   AC sys 1                         AC sys 2
     |   Conv 1      R, Ld      Conv 2   |
     +--[3-ph full]--+--/\/\--+--[3-ph full]--+
        bridge  Vd1 (+)  Id -> (+) Vd2'  bridge
                 |               |
                 +---------------+
 Vd1 = Vdo cos a1     Vd2' = -Vdo cos a2

Both converters are three-phase fully controlled bridges whose average output is Vdocos⁡αV_{do}\cos\alpha: positive for 0<α<90°0 < \alpha < 90° (rectifier) and negative for 90°<α<180°90° < \alpha < 180° (inverter).

Operation

Let both converters have the same no-load voltage Vdo=32VLπV_{do} = \dfrac{3\sqrt{2}V_L}{\pi} and the line resistance be RR. Converter 1 gives Vd1=Vdocos⁡α1V_{d1} = V_{do}\cos\alpha_1. Converter 2 is connected in opposition, so its terminal voltage seen by the line is Vd2′=−Vdocos⁡α2V_{d2}' = -V_{do}\cos\alpha_2. Thyristors allow current IdI_d in one direction only:

Id=Vd1−Vd2′R=Vdo(cos⁡α1+cos⁡α2)R≥0I_d = \frac{V_{d1} - V_{d2}'}{R} = \frac{V_{do}(\cos\alpha_1 + \cos\alpha_2)}{R} \ge 0

Power sent by converter 1 and received by converter 2:

P1=Vdocos⁡α1 Id,P2=−Vdocos⁡α2 Id,P1−P2=Id2RP_1 = V_{do}\cos\alpha_1\,I_d, \qquad P_2 = -V_{do}\cos\alpha_2\,I_d, \qquad P_1 - P_2 = I_d^2R

Case 1: power from system 1 to system 2.

  • α1<90°\alpha_1 < 90°: converter 1 is a rectifier (Vd1>0V_{d1} > 0, P1>0P_1 > 0).
  • α2>90°\alpha_2 > 90°: converter 2 is an inverter (cos⁡α2<0\cos\alpha_2 < 0, P2>0P_2 > 0 delivered to system 2).
  • Line voltage is positive at the top conductor.

Case 2: power from system 2 to system 1 (reversal).

  • Make α1>90°\alpha_1 > 90°: converter 1 becomes an inverter (Vd1<0V_{d1} < 0).
  • Make α2<90°\alpha_2 < 90°: converter 2 becomes a rectifier.
  • The current direction stays the same; only the polarity of the DC line voltage reverses, so P=VdIdP = V_dI_d changes sign.

Condition for current flow in both cases:

cos⁡α1+cos⁡α2>0  ⇒  cos⁡α1>cos⁡(180°−α2)  ⇒  α1+α2<180°\cos\alpha_1 + \cos\alpha_2 > 0 \;\Rightarrow\; \cos\alpha_1 > \cos(180° - \alpha_2) \;\Rightarrow\; \alpha_1 + \alpha_2 < 180°

For a line of small resistance, IdRI_dR is small, so

α1+α2≈180°,i.e. α2≈180°−α1\alpha_1 + \alpha_2 \approx 180°, \quad \text{i.e. } \alpha_2 \approx 180° - \alpha_1

The magnitude of IdI_d (and power) is set by how much α1+α2\alpha_1 + \alpha_2 is less than 180°180°; the direction of power is set by which converter has α<90°\alpha < 90°.

Modeα1\alpha_1α2\alpha_2Line polarityPower
Normal<90°< 90° (rectifier)>90°> 90° (inverter)+1 → 2
Reversed>90°> 90° (inverter)<90°< 90° (rectifier)−2 → 1

Practical sequence for reversal

  1. Reduce the current order to a minimum value.
  2. Increase α1\alpha_1 beyond 90°90° and decrease α2\alpha_2 below 90°90° gradually; the line voltage passes through zero and reverses.
  3. Raise the current order again; power now flows from system 2 to system 1.

No switching of conductors is needed and reversal takes only a fraction of a second, which is an important advantage of HVDC links.

  • 2072 Chaitra · 8 marks

Justify the statement "HVDC power transmission is only economical than HVAC transmission if bulk amount of power has to be transmitted over a long distance". And also justify that the power transmission capacity of HVDC and HVAC lines are equal.

Answer

HVDC needs costly converter stations (thyristor valves, converter transformers, filters, reactive compensation) at both ends, but its line is cheaper per km and has lower losses. So HVDC becomes economical only when the line saving is large enough to pay for the terminals, i.e. for bulk power over a long distance.

Justification of the statement

  • Terminal cost: HVDC terminal cost is much higher than AC substations. This is a fixed cost, independent of distance.
  • Line cost: DC line needs 2 conductors instead of 3, lighter towers, less insulation and narrower right of way, so cost per km is lower. Its losses are about 2/3 of AC.
  • Total cost = terminal cost + (cost per km × distance). The AC curve starts low but rises steeply; the DC curve starts high but rises slowly. They cross at the break-even distance (about 500–800 km for overhead lines, 40–80 km for cables).
 Cost
  |                      / AC
  |                    /
  |                  /    _____ DC
  |            _____X-----
  |     _____-    / :
  | DC -        /   :
  |           /     :
  |  AC     /       :
  |       /         :
  |     /           :
  +-----------------:------> km
             break-even distance
  • Power level: converter cost per MW falls as rating rises, and the 2-conductor saving grows with power; for small power the fixed terminal cost cannot be recovered.
  • Also, long AC lines need series and shunt compensation and are stability-limited (P=V1V2Xsin⁡δP = \frac{V_1V_2}{X}\sin\delta), adding cost; DC has no such limit.

So HVDC is cheaper than HVAC only when large power is sent beyond the break-even distance (or for long cables / asynchronous links).

Power transmission capacity of HVDC and HVAC lines are equal

Assumptions: same conductor size and current II, same insulation (peak voltage to earth VmV_m), DC voltage Vd=VmV_d = V_m, Id=II_d = I.

Pac=3⋅Vm2⋅Icos⁡ϕ=2.121 VmIcos⁡ϕPdc=2VdId=2VmIPdcPac=0.943cos⁡ϕ\begin{aligned} P_{ac} &= 3\cdot\frac{V_m}{\sqrt{2}}\cdot I\cos\phi = 2.121\,V_mI\cos\phi \\ P_{dc} &= 2V_dI_d = 2V_mI \\ \frac{P_{dc}}{P_{ac}} &= \frac{0.943}{\cos\phi} \end{aligned}

For a normal power factor of cos⁡ϕ=0.943\cos\phi = 0.943, Pdc=PacP_{dc} = P_{ac}. Thus a bipolar DC line with 2 conductors has the same capacity as a three-phase AC line with 3 conductors, while its losses are 2I2R2I^2R against 3I2R3I^2R (2/3) and it saves one conductor and its insulators.

  • 2070 Chaitra · 8 marks

Explain the process of reversible power flow on HVDC line and obtain the relation between firing angle of both converters.

Answer

In an HVDC line, the converters at both ends are fully controlled thyristor bridges. Thyristors pass current in one direction only, so power reversal is done by reversing the DC voltage polarity using the firing angles, not by reversing the current.

Circuit

   AC sys 1                         AC sys 2
     |   Conv 1      R, Ld      Conv 2   |
     +--[3-ph full]--+--/\/\--+--[3-ph full]--+
        bridge  Vd1 (+)  Id -> (+) Vd2'  bridge
                 |               |
                 +---------------+
 Vd1 = Vdo cos a1     Vd2' = -Vdo cos a2

Process and firing angle relation

Let both converters have the same no-load voltage Vdo=32VLπV_{do} = \dfrac{3\sqrt{2}V_L}{\pi} and the line resistance be RR. Converter 1 gives Vd1=Vdocos⁡α1V_{d1} = V_{do}\cos\alpha_1. Converter 2 is connected in opposition, so its terminal voltage seen by the line is Vd2′=−Vdocos⁡α2V_{d2}' = -V_{do}\cos\alpha_2. Thyristors allow current IdI_d in one direction only:

Id=Vd1−Vd2′R=Vdo(cos⁡α1+cos⁡α2)R≥0I_d = \frac{V_{d1} - V_{d2}'}{R} = \frac{V_{do}(\cos\alpha_1 + \cos\alpha_2)}{R} \ge 0

Power sent by converter 1 and received by converter 2:

P1=Vdocos⁡α1 Id,P2=−Vdocos⁡α2 Id,P1−P2=Id2RP_1 = V_{do}\cos\alpha_1\,I_d, \qquad P_2 = -V_{do}\cos\alpha_2\,I_d, \qquad P_1 - P_2 = I_d^2R

Case 1: power from system 1 to system 2.

  • α1<90°\alpha_1 < 90°: converter 1 is a rectifier (Vd1>0V_{d1} > 0, P1>0P_1 > 0).
  • α2>90°\alpha_2 > 90°: converter 2 is an inverter (cos⁡α2<0\cos\alpha_2 < 0, P2>0P_2 > 0 delivered to system 2).
  • Line voltage is positive at the top conductor.

Case 2: power from system 2 to system 1 (reversal).

  • Make α1>90°\alpha_1 > 90°: converter 1 becomes an inverter (Vd1<0V_{d1} < 0).
  • Make α2<90°\alpha_2 < 90°: converter 2 becomes a rectifier.
  • The current direction stays the same; only the polarity of the DC line voltage reverses, so P=VdIdP = V_dI_d changes sign.

Condition for current flow in both cases:

cos⁡α1+cos⁡α2>0  ⇒  cos⁡α1>cos⁡(180°−α2)  ⇒  α1+α2<180°\cos\alpha_1 + \cos\alpha_2 > 0 \;\Rightarrow\; \cos\alpha_1 > \cos(180° - \alpha_2) \;\Rightarrow\; \alpha_1 + \alpha_2 < 180°

For a line of small resistance, IdRI_dR is small, so

α1+α2≈180°,i.e. α2≈180°−α1\alpha_1 + \alpha_2 \approx 180°, \quad \text{i.e. } \alpha_2 \approx 180° - \alpha_1

The magnitude of IdI_d (and power) is set by how much α1+α2\alpha_1 + \alpha_2 is less than 180°180°; the direction of power is set by which converter has α<90°\alpha < 90°.

Modeα1\alpha_1α2\alpha_2Line polarityPower
Normal<90°< 90° (rectifier)>90°> 90° (inverter)+1 → 2
Reversed>90°> 90° (inverter)<90°< 90° (rectifier)−2 → 1

Waveform idea

 Vd
 +|----____        normal (1 -> 2)
  |        \
 0+---------\----------- time
  |          \____     reversed (2 -> 1)
 -|
 Id  constant direction throughout

Result: current flows only if α1+α2<180°\alpha_1 + \alpha_2 < 180°; for a low-resistance line α2≈180°−α1\alpha_2 \approx 180° - \alpha_1, and the converter with α<90°\alpha < 90° is the sending end.

Questions from Old Question Collection (EE 701) (IOE BEL EE 701 exam papers from 2073 Shrawan to 2082 Baishakh) and Question bank (ioesolutions) (IOE BEL EE 701 exam papers from 2069 Chaitra to 2073 Chaitra). Answers are written for this site; check them against your class notes.

Chapter titles and hours from the IOE syllabus ↗