Fire fighting system in power station
Short answer
The fire-fighting system uses smoke/heat detectors and an alarm panel to trip equipment and start extinguishing. Transformer fires are fought with water spray (deluge) to emulsify oil, CO2 flooding protects generators and cable rooms, and a hydrant ring with pumps supplies water. Portable extinguishers and passive measures are also used.
Describe the fire fighting system used in power station with necessary diagram.
The fire fighting system of a power station detects a fire early, raises an alarm and puts it out quickly, so that costly equipment (transformers, generators, cable galleries, oil stores) is saved and people are safe.
Main fire risks
- Transformer and switchgear insulating oil
- Generator windings (insulation, and hydrogen in large units)
- Cable trenches and galleries
- Fuel oil and coal stores, battery rooms
Components of the system
+--------+ +-------------+ +-----------------+
| Fire |-->| Fire alarm |-->| Alarm (bells, |
|detector| | control pnl | | lamps) + trip |
+--------+ +------+------+ +-----------------+
| opens deluge valve
+-------+ +-------+v +-------+ +-----------+
| Water |->| Pumps |->|Deluge |-->| Spray |
| tank | |(el+DG)| | valve | | nozzles |
+-------+ +-------+ +-------+ | (on xfmr) |
+-----------+
- Detection: smoke, heat (rate-of-rise) and flame detectors; for transformers, quartz bulb or linear heat detectors placed around the tank.
- Alarm panel: receives detector signals, sounds the alarm, shows the zone, trips the equipment and starts the extinguishing system.
- Extinguishing systems:
- Hydrant system: a ring main of pipes with hydrant points and hoses, kept pressurised by a jockey pump, with a main electric pump and a standby diesel pump.
- Water spray (deluge) / mulsifire system: for transformers; a high-velocity water spray forms an emulsion on the oil surface, cools it and cuts off oxygen.
- CO flooding system: for generators, control rooms and cable vaults; CO cylinders discharge automatically and dilute the oxygen. Used where water would damage equipment.
- Foam system: for oil tanks and fuel stores.
- Portable extinguishers: CO, dry chemical powder and foam types near equipment.
- Passive measures: oil soak pits filled with gravel under transformers, fire walls between transformers, fire-resistant cable coating and fire barriers.
Requirements
- Automatic operation with manual back-up.
- A reliable, separate water supply and a standby diesel pump.
- Regular testing of detectors, pumps and cylinders.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Requirements of steam power station design · Power Plant Equipment, chapter 7
- Reactor to protect circuit breaker of small station · Power Plant Equipment, chapter 4
- SCADA in a power system · Power Plant Equipment, chapter 4 · asked 4×
- Function of reactor in power system · Power Plant Equipment, chapter 4 · asked 3×
- Why reactors are used and their types · Power Plant Equipment, chapter 4
- Function of excitation system and its transfer function · Power Plant Equipment, chapter 3 · asked 2×
- Electrification system and fire protection · Building Technology, chapter 12
- Major components of a power station · Power System Analysis I, chapter 1 · asked 2×
- DC supply system in a generating station · Power Plant Design, chapter 4
- Major components of a power station and functions · Power System Analysis I, chapter 1