Fire fighting system in power station

Short answer

The fire-fighting system uses smoke/heat detectors and an alarm panel to trip equipment and start extinguishing. Transformer fires are fought with water spray (deluge) to emulsify oil, CO2 flooding protects generators and cable rooms, and a hydrant ring with pumps supplies water. Portable extinguishers and passive measures are also used.

Describe the fire fighting system used in power station with necessary diagram.

The fire fighting system of a power station detects a fire early, raises an alarm and puts it out quickly, so that costly equipment (transformers, generators, cable galleries, oil stores) is saved and people are safe.

Main fire risks

  • Transformer and switchgear insulating oil
  • Generator windings (insulation, and hydrogen in large units)
  • Cable trenches and galleries
  • Fuel oil and coal stores, battery rooms

Components of the system

 +--------+   +-------------+   +-----------------+
 | Fire   |-->| Fire alarm  |-->| Alarm (bells,   |
 |detector|   | control pnl |   | lamps) + trip   |
 +--------+   +------+------+   +-----------------+
                     | opens deluge valve
 +-------+  +-------+v +-------+   +-----------+
 | Water |->| Pumps |->|Deluge |-->| Spray     |
 | tank  |  |(el+DG)|  | valve |   | nozzles   |
 +-------+  +-------+  +-------+   | (on xfmr) |
                                   +-----------+
  1. Detection: smoke, heat (rate-of-rise) and flame detectors; for transformers, quartz bulb or linear heat detectors placed around the tank.
  2. Alarm panel: receives detector signals, sounds the alarm, shows the zone, trips the equipment and starts the extinguishing system.
  3. Extinguishing systems:
    • Hydrant system: a ring main of pipes with hydrant points and hoses, kept pressurised by a jockey pump, with a main electric pump and a standby diesel pump.
    • Water spray (deluge) / mulsifire system: for transformers; a high-velocity water spray forms an emulsion on the oil surface, cools it and cuts off oxygen.
    • CO2_2 flooding system: for generators, control rooms and cable vaults; CO2_2 cylinders discharge automatically and dilute the oxygen. Used where water would damage equipment.
    • Foam system: for oil tanks and fuel stores.
    • Portable extinguishers: CO2_2, dry chemical powder and foam types near equipment.
  4. Passive measures: oil soak pits filled with gravel under transformers, fire walls between transformers, fire-resistant cable coating and fire barriers.

Requirements

  • Automatic operation with manual back-up.
  • A reliable, separate water supply and a standby diesel pump.
  • Regular testing of detectors, pumps and cylinders.