Open loop and closed loop V/f inverter-fed drive

Short answer

Open-loop V/f control keeps flux constant but speed drops with load, can stall on fast changes, and has no current limit. Closed loop measures speed, a PI controller sets a limited slip frequency, and inverter frequency equals rotor speed plus slip, restoring speed and limiting torque and current.

Discuss the operation of open loop V/F control of inverter fed induction machine drive. What are problem with it? How do you overcome this effect by closed loop operation, explain it with closed loop block diagram.

Open-loop V/f control

A voltage source (PWM) inverter feeds the induction motor. The speed command sets the inverter frequency ff; a function generator sets the voltage so that V/fV/f is constant (with a small boost at low frequency for the I1R1I_1R_1 drop). The air-gap flux is then nearly constant and the motor runs close to Ns=120f/PN_s = 120f/P.

 speed   +------+  f*  +----------+  V*  +---------+    +----+
 ref --->| ramp |--+-->| V/f      |----->| PWM VSI |--->| IM |
         +------+  |   | function |      +---------+    +----+
                   |   +----------+        ^     ^
                   +-----------------------+     |
                              f*                 | dc link
                         ac -> rectifier --------+
  • Simple, cheap, no speed sensor; good for fans, pumps, and many motors on one inverter.
  • A ramp (soft start) limits the rate of change of ff so that the slip stays small.

Problems of open-loop operation

  1. Speed error with load: the motor speed N=Ns(1−s)N = N_s(1-s) falls as the load increases; there is no correction, so speed regulation is poor.
  2. Pull-out/instability: if the frequency changes too fast, or a sudden load is applied, the slip exceeds the breakdown slip and the motor stalls or draws very high current.
  3. No current limit: overcurrent during fast acceleration or braking.
  4. Low-speed weakness: at low frequency the stator drop reduces flux and torque; a fixed boost may over- or under-flux the motor.
  5. Poor dynamic response; the drive may oscillate at light load.

Closed-loop operation (slip regulation)

Speed is measured by a tachogenerator/encoder and compared with the reference. The speed error, through a PI controller, sets the slip speed ωsl∗\omega_{sl}^*, which is limited to a safe value. The inverter frequency is

ωe∗=ωr+ωsl∗\omega_e^* = \omega_r + \omega_{sl}^*

Since torque ∝ωsl\propto \omega_{sl} at constant flux, limiting the slip limits the torque and current.

 w_r* +    +----+  w_sl*  +-----+ +   w_e*   +-----+  V*  +-----+
 ---->(O)->| PI |-------->|limit|-->(O)------>| V/f |----->| PWM |-> IM
      -|   +----+         +-----+    ^ +      +-----+  f*  | VSI |   |
       |                             |                     +-----+   |
       +-------------------- w_r ---+---------- tacho <--------------+
  • On a load increase, the speed falls, the error rises, and the slip and frequency increase until the speed is restored, so speed regulation is very good.
  • The slip limit keeps the motor below breakdown slip, giving fast acceleration and braking at the maximum allowed torque without stalling.
  • The voltage is taken from ωe∗\omega_e^* through the V/f function, so the flux stays constant.
  • A negative slip limit allows regenerative braking (with a suitable dc link).
  • An inner current loop may be added for direct current limiting.