Variable frequency control of induction motor

Short answer

Variable frequency control changes synchronous speed by changing stator frequency; below base speed V/f is kept constant to maintain flux and constant maximum torque. Above base speed voltage is fixed, flux weakens, giving constant power operation, and voltage boost compensates stator resistance drop at low frequency.

How three phase induction motor has controlled by variable frequency method? Explain with necessary mathematical relation and figures.

In variable frequency control, the stator supply frequency is changed by an inverter so that the synchronous speed Ns=120f/PN_s = 120f/P changes, and the motor speed changes with it at small slip. To keep the flux constant, the voltage is changed in proportion to frequency (V/f control).

Why voltage must change with frequency

Stator induced emf: E1=4.44 f N1ϕ kwE_1 = 4.44\, f\, N_1 \phi\, k_w, so

ϕ∝E1f≈Vf\phi \propto \frac{E_1}{f} \approx \frac{V}{f}
  • If ff is reduced at constant VV, the flux rises, the core saturates and the magnetising current becomes very large.
  • If ff is raised at constant VV, the flux falls and the torque capability falls.

Hence, below base frequency, V/fV/f is kept constant.

Torque relations

Neglecting the stator impedance, the torque at slip ss (slip speed ωsl=sωs\omega_{sl} = s\omega_s) is

T=3ωsV2(R2′/s)(R2′/s)2+X2′2T = \frac{3}{\omega_s}\frac{V^2 (R_2'/s)}{(R_2'/s)^2 + X_2'^2}

With X2′∝fX_2' \propto f, the maximum torque is

Tmax=32ωsV2X2′∝(Vf)2T_{max} = \frac{3}{2\omega_s}\frac{V^2}{X_2'} \propto \left(\frac{V}{f}\right)^2

So with constant V/fV/f, TmaxT_{max} is constant at all frequencies, and the slip speed at TmaxT_{max}, smωs=R2′ωs/X2′s_m\omega_s = R_2'\omega_s/X_2', is also constant. The speed–torque curves simply shift parallel to each other.

Operating regions

 V, T, P
  |        ____________ V (rated)
  |      /|
  |    /  |  T falls ~1/f
  |  /    |____________ P constant
  |/______|____________ T constant
  +-------+----------> f
       base f (50 Hz)
 constant torque | constant power
 (V/f const)     | (V fixed, field weak)
  • Below base speed: V/fV/f constant; constant torque region.
  • Above base speed: the voltage cannot exceed rated, so VV is fixed and ff is increased; the flux falls (ϕ∝1/f\phi \propto 1/f), giving the constant power (field weakening) region with Tmax∝1/f2T_{max} \propto 1/f^2.
  • At very low frequency the stator I1R1I_1R_1 drop is significant, so a voltage boost is added to keep the flux.

Converter

 ac -> [rectifier] -> [dc link] -> [PWM inverter] -> IM
                         V/f reference and firing logic

A PWM voltage source inverter (or a cycloconverter for very low speeds) supplies variable voltage and frequency.

Advantages: wide speed range above and below base speed, high efficiency (low slip), smooth starting with full torque at low current, regenerative braking possible; suitable for cage motors. Drawbacks: costly power electronics and harmonics.