Starting induction motor with variable frequency
Short answer
Starting at low frequency raises flux (φ ∝ V/f), causing saturation and high magnetizing current if voltage is not reduced. The problem is overcome by constant V/f control with low-frequency voltage boost (IR compensation) and starting at a frequency where slip for maximum torque equals 1, then ramping up frequency.
What happen if an induction motor is started with variable frequency? What is the technique to overcome the problems associated with variable frequency? Justify your answer with suitable mathematical expression.
Starting an induction motor from a variable frequency supply (low frequency at first, then raised) gives a high starting torque with low starting current, because at low frequency the synchronous speed is low and the rotor slip frequency is small. But if only frequency is reduced while voltage is kept constant, the motor is over-fluxed and draws a very high magnetising current.
What happens at low frequency
Stator emf:
- Constant V, low f: becomes many times rated; the core saturates, the magnetising current and iron loss rise sharply, the motor overheats. Also reactances fall, so the current rises further.
- High slip at start on full frequency: at 50 Hz direct start, , rotor current is 5–7 times rated while torque is small (rotor pf low).
- Stator resistance effect: at low frequency becomes comparable to the reactance; with pure V/f, the drop is a large fraction of , so flux and maximum torque fall:
At rated frequency and ; at low , the terms do not reduce with , so drops.
Technique to overcome these problems
- Constant V/f control: change voltage in proportion to frequency, = constant, so flux stays at rated value and is (nearly) the same at every frequency.
- Low-frequency voltage boost (IR compensation): add a fixed voltage at low frequency,
so that , not , is held constant. 3. Start at a frequency giving maximum torque at standstill. Slip for maximum torque (approx.) . With , choose the start frequency such that :
The motor then starts with at modest current. The frequency is ramped up (soft start) so that slip speed stays small and current stays near rated. 4. Closed-loop slip/current limit: the controller limits slip frequency ; since and depends on , the motor accelerates at controlled torque and current.
Thus V/f control with boost and a frequency ramp gives a smooth start with high torque and low current, which a direct-on-line start cannot give.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Variable frequency control of induction motor · Utilization of Electrical Energy, chapter 3
- Justify: series motor power; shunt motor for traction · Utilization of Electrical Energy, chapter 4
- Low frequency induction furnace with half-full hearth · Utilization of Electrical Energy, chapter 5 · asked 2×
- DC shunt motor speed at reduced voltage and starting resistance · Utilization of Electrical Energy, chapter 3
- Capacitor bank for 340 kW induction motor · Utilization of Electrical Energy, chapter 6 · asked 2×
- Induction motor with square-law load: voltage at 1300 rpm · Utilization of Electrical Energy, chapter 3
- Justify synchronous motor is not self starting · Electric Machines II, chapter 2
- Need of starter and induction motor starting methods · Electrical Machines I, chapter 5
- True/false: series motor started at no load · Electrical Machine, chapter 4
- DC series motor started at no load: true/false · Electrical Machines, chapter 4