- 2079 Bhadra · 8 marks
Which motor is more economical (two-part tariff)
Short answer
Annual cost is demand charge (Rs 250 per kVA) plus energy charge (Rs 8 per kWh) plus capital charges. Both motors draw 45.75 kVA. Motor A: 41.18 kW input, total Rs 999,823. Motor B: 38.89 kW input with condenser, total Rs 944,974. Motor B is more economical by Rs 54,849 per year.
A consumer requires an induction motor of 35 kW. He is offered two motors of the following specifications. Motor A: Efficiency = 85%; power factor 0.9 Motor B: Efficiency = 90%; power factor 0.8 The consumer is being charged on a two-part tariff of Rs. 250 per kVA of the maximum demand plus Rs. 8 per unit. The power factor of the motor B is to be raised to 0.85 by installing condensers. The motor costs Rs. 1500 less than motor A. The cost of condenser is Rs. 400 per kVAR. Determine which motor is more economical. Assume rate of interest and depreciation as 10% and working hours of motors as 3000 hours in a year.
Compare the annual cost of each motor: demand charge + energy charge + interest and depreciation on the extra capital. The tariff of Rs 250 per kVA of maximum demand is taken as an annual charge, and "the motor costs Rs 1500 less" is read as motor B costs Rs 1500 less than motor A.
Motor A ( = 85%, pf = 0.9)
Annual cost of A = 11,438 + 988,235 + 150 = Rs 999,823
Motor B ( = 90%, pf raised from 0.8 to 0.85)
Annual cost of B = 11,438 + 933,333 + 202.6 = Rs 944,974
Comparison
| Item | Motor A | Motor B |
|---|---|---|
| Input (kW) | 41.18 | 38.89 |
| Max demand (kVA) | 45.75 | 45.75 |
| Demand charge (Rs) | 11,438 | 11,438 |
| Energy charge (Rs) | 988,235 | 933,333 |
| Capital charge (Rs) | 150 | 202.6 |
| Total (Rs/year) | 999,823 | 944,974 |
Both motors draw the same kVA, so the higher efficiency of B decides the result.
Answer: Motor B (with condensers) is more economical, saving about Rs 54,849 per year.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Line pf of 35 kW induction motor with capacitors · Utilization of Electrical Energy, chapter 6 · asked 3×
- Capacitor bank for 340 kW induction motor · Utilization of Electrical Energy, chapter 6 · asked 2×
- Factors of tariff; two-part and time of day tariff · Utilization of Electrical Energy, chapter 6
- Annual charge and pf improvement (Rs 1300/kVA tariff) · Utilization of Electrical Energy, chapter 6 · asked 3×
- Annual charge and pf improvement (Rs 65/kVA tariff) · Utilization of Electrical Energy, chapter 6 · asked 3×
- Slip power recovery for slip ring induction motor · Utilization of Electrical Energy, chapter 3 · asked 2×
- Optimum pf under two-part tariff (200 kW) · Industrial Power Distribution and Illumination, chapter 10
- Rotor copper loss and efficiency of 35 kW induction motor · Electrical Machines I, chapter 5
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- 2.2 kW cage motor designed for best power factor · Electric Machine Design, chapter 4 · asked 2×