Measurement of dielectric constant and loss factor
Short answer
Schering bridge measures Cx = Cs R4/R3 and tan δ = ω C4 R4; with guard-ring electrode, εr = Cx d/(ε0 A) and loss factor εr tan δ. Transformer ratio-arm bridge and Q-meter are alternatives. Tan δ rise with voltage indicates voids, with temperature indicates ageing.
Describe the methods for measurement of dielectric constant and loss factor.
The dielectric constant () of an insulating material is the ratio of the capacitance of a specimen to its capacitance with vacuum (air) as dielectric. The loss factor is , where (dissipation factor) is the ratio of the loss (resistive) current to the charging (capacitive) current. Both are measured by bridge methods at power and higher frequencies; the most common is the high-voltage Schering bridge.
Ix Ic (leading by 90 deg)
\ |
\ | delta = angle between
\ | Ix and Ic
\d |
\ |
------+--------> Ir (in phase with V)
1. High-voltage Schering bridge
HV supply (V)
/ \
Arm 1 / \ Arm 2
Cx + Rx Cs (standard,
(specimen) loss-free)
| |
A------[ D ]--------B
| |
Arm 3: R3 Arm 4: R4 || C4
\ /
----- earth ----
- Arm 1: test specimen, represented as in series with .
- Arm 2: standard compressed-gas capacitor (loss-free).
- Arm 3: variable non-inductive resistance .
- Arm 4: fixed resistance in parallel with a variable capacitor .
- D: vibration galvanometer or electronic null detector.
- Arms 3 and 4 are at low voltage (near earth), so adjustments are safe; protective gaps across them guard against a breakdown of or . Earthed shields (Wagner earth) remove errors due to stray capacitance.
Balance condition :
Equating real and imaginary parts:
Usually is a fixed value such as . At 50 Hz, , so (with in μF), and the dial can be calibrated directly in . (With , in μF.)
Dielectric constant: with specimen thickness and electrode area , , and
A three-terminal (guard-ring) electrode system is used so that surface leakage and edge fringing do not affect the result.
2. Transformer ratio-arm bridge
- Uses a precision ratio transformer (ratio arms) instead of resistive arms; balance is set by turns ratios .
- and from the conductance balance.
- Advantages: very high accuracy, unaffected by stray capacitances to earth, can test earthed specimens, works over a wide frequency range.
3. Other methods
- Resonance (Q-meter) method for high frequencies (kHz–MHz): change in resonance capacitance gives , change in Q gives .
- Measurements versus voltage and temperature: rising with voltage ("tip-up") indicates voids and partial discharge; rising with temperature indicates moisture and ageing.
| Quantity | Formula | Typical good value |
|---|---|---|
| (oil-paper bushing) | < 0.005–0.007 | |
| (transformer oil) | about 2.2 | |
| (porcelain) | about 6 |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Dielectric power loss under AC and DC · High Voltage Engineering, chapter 6
- Power loss in a glass dielectric · Electrical Engineering Material, chapter 3
- Loss tangent and dielectric power loss · Electrical Engineering Material, chapter 3 · asked 5×
- T/F: LLF unity for constant power loss · Transmission and Distribution System Design, chapter 6
- Stadia interval factor, additive constant · Surveying II, chapter 2