Improper earthing and unsafe step/touch potential
Short answer
Fault current raises the ground to GPR=IgRg, producing dangerous voltages. Touch potential is between hand on earthed metal and feet 1 m away, with body current Etouch/(Rb+1.5ρs); step potential is between feet 1 m apart, with Estep/(Rb+6ρs). Safe IEEE 80 limits are (1000+1.5Csρs)0.116/√t and (1000+6Csρs)0.116/√t; high Rg, wide mesh and no surface layer make them unsafe.
Explain how Improper Earthing may result in step potential and touch potential beyond safe value in power system with necessary diagram and formulae.
When an earth fault occurs, fault current enters the soil through the earth electrode or substation grid. The grid rises to the ground potential rise
and the ground surface potential falls with distance from the electrode. A person bridging part of this potential gets a shock. Improper earthing (high , too few electrodes, wide mesh, no bonding, no surface layer, slow protection) makes these potentials exceed the safe values.
V
|\_ GPR = Ig Rg
| \ steep gradient
| \__ (poor earthing)
| \___
| Et \____ Es
+---|--|-----|-|------> distance
structure feet 1 m apart
Touch potential
Voltage between the hand on an earthed structure and the feet standing 1 m away. Equivalent circuit: body resistance in series with two feet in parallel (), where :
Step potential
Voltage between two feet 1 m apart. Body in series with two feet ():
Safe (tolerable) limits (IEEE 80, 50 kg person)
Using Dalziel's current and :
is the surface-layer derating factor and the fault duration.
How improper earthing makes them unsafe
- High grid resistance : GPR is large, so actual touch voltage (a fraction of GPR) is large. For example, kA and gives GPR = 10 kV; even 30% of this (3 kV) as touch voltage is far above the safe value of a few hundred volts.
- Wide mesh or no grid: surface potential is not uniform; mesh (touch) voltage
rises when the total buried length is small. 3. Steep gradient at the edge (no grading ring): high step voltage
- No surface layer of crushed rock: low , so tolerable voltages drop.
- Unbonded equipment or fences: the full GPR may appear as touch voltage.
- High reduces fault current so relays may be slow; longer lowers the tolerable limits.
Remedies
Lower (more rods, larger grid, deep electrodes, chemical backfill), closer mesh spacing, bonding of all metal parts, a crushed-rock surface layer, grading rings, and fast fault clearing so that .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Improper earthing and system grounding practice · High Voltage Engineering, chapter 2
- Touch and step potential phenomenon · High Voltage Engineering, chapter 2
- Step and touch potentials, shock and safety · High Voltage Engineering, chapter 2
- Step and touch potential in mat design · Power Plant Design, chapter 4
- Types of earthing system · Industrial Power Distribution and Illumination, chapter 2
- Purpose of earthing, earthed vs unearthed system · Industrial Power Distribution and Illumination, chapter 2