Improper earthing and system grounding practice
Short answer
Improper earthing gives high ground resistance R_g, so fault current I_f produces high ground potential rise V = I_f R_g, causing dangerous touch/step voltages and failure to trip fuses. Common practice includes solid earthing of transformer neutrals at transmission voltage, resistance earthing for distribution, LV neutral solid earth, and substation earth mats per IEEE 80.
Improper Earthing leads to high electric potential, justify. Also explain how the system grounding have been incorporated in common practice?
Why improper earthing leads to high electric potential
When an earth fault occurs, the fault current flows through the earth electrode of resistance . The electrode and all connected metal parts rise to the ground potential rise (GPR):
- If the earthing is poor (high due to dry soil, corroded or loose connections, too few electrodes), becomes large. For example, A with gives kV on the equipment frame, while with it is only 1 kV.
- High also limits the fault current, so fuses or relays may not trip, and the frame stays live for a long time.
- If the frame is not earthed at all, a body touching it becomes the only path to earth and gets the full phase voltage.
- Poor earth-mat design gives steep surface voltage gradients, so step and touch potentials exceed safe values.
- In ungrounded systems an earth fault raises healthy-phase voltage to line value, and arcing grounds can produce 5–6 pu overvoltages.
- Lightning current through a high tower footing resistance causes high tower-top voltage and back-flashover.
So improper earthing creates dangerous potentials on equipment and ground, threatens people and damages insulation.
System grounding in common practice
- Generators: neutral earthed through a high resistance or a distribution transformer with a secondary resistor, to limit stator earth-fault current to a few amperes.
- Transmission (66 kV and above): solid (effective) earthing of transformer neutrals, so that healthy-phase voltage stays below 80% of line voltage (, ). This allows reduced insulation and surge arrester ratings. NEA's 132/220/400 kV systems are effectively earthed.
- Distribution (11/33 kV): solid earthing, or resistance/reactance earthing to limit fault current; resonant (Petersen coil) earthing is used in some countries for overhead networks.
- LV (400/230 V): neutral solidly earthed at the transformer (TN or TT systems); consumer installations have equipment earthing and RCDs.
- Delta systems: a zig-zag earthing transformer provides an artificial neutral.
- Substations: an earth mat (grid) of copper or GI conductors buried 0.5–1 m deep, with earth rods, bonding all equipment frames, fences and structures, covered with crushed gravel; designed per IEEE 80 so that step and touch voltages are safe.
- Transmission lines: overhead earth wires bonded to each tower; tower footing resistance kept low (below about 10–20 Ω) with rods or counterpoises.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Improper earthing and unsafe step/touch potential · High Voltage Engineering, chapter 2
- Causes of high gradient electric fields · High Voltage Engineering, chapter 5 · asked 2×
- Earthing techniques and substation safety · High Voltage Engineering, chapter 2
- Electric dipole potential and field · Electromagnetism, chapter 2 · asked 4×
- Potential of electric quadrupole on axis · Engineering Physics, chapter 7 · asked 3×
- Potential gradient gives electric field · Electromagnetism, chapter 2
- Purpose of earthing, earthed vs unearthed system · Industrial Power Distribution and Illumination, chapter 2