Civil, mechanical and electrical components

Short answer

Hydropower plant has civil components (dam, intake, desander, headrace, surge tank/forebay, powerhouse, tailrace), mechanical (penstock, valve, turbine, governor, draft tube), electrical (generator, excitation, transformer, switchyard). Water flows from reservoir through intake, tunnel, surge tank, penstock to turbine, then tailrace.

Draw schematic diagram of a hydropower plant and explain the basic civil, mechanical and electrical components used.

A hydropower plant converts the potential energy of water into electricity. Its works are grouped into civil, mechanical and electrical components.

 River/Reservoir
  ==|== Dam/weir             [CIVIL]
     |  Intake, desander
     |  Headrace tunnel/canal
     |  Surge tank / forebay
     v
  Penstock -> Valve          [MECH]
     v
  Turbine ---- Generator     [MECH] [ELEC]
     |  Governor  |  Excitation
  Draft tube      v
     |        GCB -> GSU transformer
  Tailrace        v           [ELEC]
     v        Switchyard -> Transmission line
   River

Civil components

  • Dam / diversion weir: raises water level, creates head or storage; includes spillway and undersluice.
  • Intake: trash rack and gates admit design flow.
  • Gravel trap and desander: remove sediment.
  • Headrace canal or tunnel: conveys water with low head loss.
  • Forebay or surge tank: provides a free water surface, absorbs water hammer.
  • Powerhouse: building or cavern for units, crane and control room.
  • Tailrace: returns water to the river.
  • Access roads, anchor blocks and saddles for the penstock.

Mechanical components

  • Penstock: steel pipe that delivers water under pressure.
  • Main inlet valve: butterfly or spherical valve.
  • Turbine: Pelton (high head), Francis (medium head), Kaplan (low head).
  • Governor: controls flow to keep speed and frequency constant.
  • Draft tube: recovers outlet energy of reaction turbines.
  • Auxiliaries: cooling water, lubrication and oil pressure units, compressed air, EOT crane, dewatering and drainage pumps, fire fighting.

Electrical components

  • Generator: synchronous, usually 11 kV.
  • Excitation system and AVR: brushless or static; control voltage and reactive power.
  • Generator circuit breaker and bus duct.
  • Generator step-up transformer: e.g. 11/132 kV.
  • Switchyard: circuit breakers, isolators, CTs, PTs, lightning arresters, busbars.
  • Auxiliary supply: station transformer, DC battery and charger, diesel generator for black start.
  • Protection, control, metering, SCADA and communication (PLCC/OPGW).
  • Earthing system: grounding mat for powerhouse and switchyard.