Spinning reserve versus reserve power

Short answer

Spinning reserve is unused capacity of synchronised running units, available in seconds to minutes, sized at least largest running unit. Reserve power is total spare capacity above peak, including spinning, non-spinning and cold reserve, typically 15-25% of peak. Spinning reserve is part of total reserve.

What is the difference between spinning reserve and reserve power?

Spinning reserve is the unused capacity of generators that are already running and synchronised to the grid, ready to pick up load within seconds to minutes. Reserve power (total reserve) is all the capacity available above the peak demand, including spinning, non-spinning (quick start) and cold reserve.

Difference

PointSpinning reserveReserve power (total reserve)
MeaningUnloaded capacity of synchronised unitsTotal spare capacity over peak demand
State of unitsRunning and connectedRunning, standby or shut down
Response timeSeconds to ~10 minSeconds to hours/days
PurposeCover sudden loss of a unit, load jumps; frequency controlCover outages, maintenance, forecast error, low hydrology
SizeUsually ≥ largest running unitUsually 15–25% of peak (reserve margin)
CostHigher (units run part-loaded)Mainly capital cost of extra plants
Planning horizonOperational (daily)Long-term planning

Example: A 1,000 MW system with 1,200 MW installed has 200 MW reserve. If units on line can deliver 1,080 MW while load is 1,000 MW, spinning reserve is 80 MW; the remaining 120 MW is non-spinning/cold reserve.