Tidal power output: 3 km × 5.5 km barrage

Short answer

A tidal barrage traps basin water at high tide and releases it through turbines when the sea falls; energy per tide is 0.5 rho g A h^2. Using area 1.65e7 m^2, height 10 m, density 1023 kg/m^3, two tides, and 60% efficiency, average power capacity is about 115 MW.

Assume that there is barrage of size 3 km × 5.5 km for tidal power project. Average number of tides per day is 2 and the tide height is 10 m. Considering power conversion efficiency of 60%, determine power output capacity of the tidal project. The density of sea water is 1023 kg/m³.

In a tidal barrage, the basin fills at high tide and the trapped water is released through turbines when the sea falls. The potential energy of water of area AA and tidal range hh (centre of mass at h/2h/2) is:

E=ρgAh⋅h2=12ρgAh2E = \rho g A h \cdot \frac{h}{2} = \frac{1}{2}\rho g A h^2

Given

  • A=3 km×5.5 km=3000×5500=1.65×107 m2A = 3\ \text{km} \times 5.5\ \text{km} = 3000 \times 5500 = 1.65\times 10^7\ \text{m}^2
  • h=10h = 10 m, ρ=1023\rho = 1023 kg/m³, g=9.81g = 9.81 m/s²
  • 2 tides per day, η=0.60\eta = 0.60

Step 1: Energy per tide

E=0.5×1023×9.81×1.65×107×102=8.279×1012 J=8.279×10123.6×109=2299.8 MWh\begin{aligned} E &= 0.5 \times 1023 \times 9.81 \times 1.65\times 10^7 \times 10^2 \\ &= 8.279 \times 10^{12}\ \text{J} \\ &= \frac{8.279\times 10^{12}}{3.6\times 10^9} = 2299.8\ \text{MWh} \end{aligned}

Step 2: Energy per day available

Eday=2×8.279×1012=1.656×1013 JE_{day} = 2 \times 8.279\times 10^{12} = 1.656\times 10^{13}\ \text{J}

Step 3: Average electrical power

P=ηEday86400=0.6×1.656×101386400=1.150×108 W=115.0 MW\begin{aligned} P &= \frac{\eta E_{day}}{86400} = \frac{0.6 \times 1.656\times 10^{13}}{86400} \\ &= 1.150\times 10^{8}\ \text{W} = 115.0\ \text{MW} \end{aligned}

Annual energy (for reference)

Eyear=115.0 MW×8760 h≈1007 GWhE_{year} = 115.0\ \text{MW} \times 8760\ \text{h} \approx 1007\ \text{GWh}

Answer: Average power output capacity ≈115\approx 115 MW (energy per tide ≈2300\approx 2300 MWh before losses).

Assumption: one emptying of the basin per tide (single-effect ebb generation), averaged over 24 hours.

✓ Answer checked by Claude Opus 5.5 (high effort)