Tidal power generation and output: 3 km × 3 km

Short answer

Tides create a head between sea and basin; water flows through low-head bulbs turbines during ebb, driving generators. Energy per tide is 0.5 rho g A h^2. With area 9e6 m^2, range 10 m, density 1025 kg/m^3, two tides daily, and 30% efficiency, average power output is about 31.4 MW.

How electric power is generated from a Tidal Power Project? Estimate the power output from a tidal project that has tidal range of approximately 10 m. The surface area of tidal harnessing plant is 3 km × 3 km. Consider that there are two high tides every day. Assume power conversion efficiency as 30%. Density of sea water is about 1025 kg/m³.

Generation of electric power from a tidal project

Tides are the periodic rise and fall of sea level caused by the moon and sun's gravity; most coasts have two high and two low tides a day. A tidal power plant uses the head between the sea and a basin.

        SEA                BARRAGE            BASIN
  high tide  ~~~~~      +-----------+
                        | sluice    |     ~~~~~ stored
  low tide   ~~~~       | turbine   |           water
                        +-----------+
   <--- flow through turbine on ebb (basin -> sea)
  1. A barrage (dam) is built across a bay or estuary, with sluice gates and low-head bulb (Kaplan type) turbines.
  2. Filling: at rising tide the gates open and the basin fills.
  3. Holding: at high tide the gates close and water is held.
  4. Generation (ebb): when the sea falls, a head forms; water flows from basin to sea through the turbines, driving generators.
  5. In double-effect schemes, power is also generated on the flood tide (sea to basin).

Examples: La Rance (France, 240 MW), Sihwa (South Korea, 254 MW).

Power estimation

Energy of water in the basin per tide (centre of gravity at h/2h/2):

E=12ρgAh2E = \frac{1}{2}\rho g A h^2

Given: A=3000×3000=9×106A = 3000 \times 3000 = 9\times 10^6 m², h=10h = 10 m, ρ=1025\rho = 1025 kg/m³, g=9.81g = 9.81 m/s², 2 tides per day, η=0.30\eta = 0.30.

E=0.5×1025×9.81×9×106×102=4.525×1012 J per tide=1256.9 MWh per tideEday=2×4.525×1012=9.050×1012 JPavg=ηEday86400=0.30×9.050×101286400=3.142×107 W\begin{aligned} E &= 0.5 \times 1025 \times 9.81 \times 9\times 10^6 \times 10^2 \\ &= 4.525\times 10^{12}\ \text{J per tide} \\ &= 1256.9\ \text{MWh per tide} \\ E_{day} &= 2 \times 4.525\times 10^{12} = 9.050\times 10^{12}\ \text{J} \\ P_{avg} &= \frac{\eta E_{day}}{86400} = \frac{0.30 \times 9.050\times 10^{12}}{86400} \\ &= 3.142\times 10^{7}\ \text{W} \end{aligned}

Answer: Average power output ≈31.4\approx 31.4 MW (about 275 GWh per year).

Assumption: one basin emptying per high tide, averaged over 24 hours.