T/F: grid connected system more stable

Short answer

True. A large grid has high total inertia and low Thevenin impedance, keeping frequency and voltage steady during disturbances. Shared spinning reserve further aids stability, though weak ties can cause oscillations if not controlled; overall it is more stable.

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: Grid connected power system is more stable.

TRUE (in general).

  • In a large grid the total inertia (∑H\sum H) of all connected machines is large, so a sudden load change or loss of a generator causes only a small change in frequency.
  • The grid's low Thevenin impedance (high SCMVA) keeps bus voltages steady during disturbances; it acts like an "infinite bus" for each small plant.
  • Spinning reserve is shared, so other plants pick up the load of a tripped unit.
  • An isolated system has small inertia and little reserve, so frequency and voltage swing much more and it can collapse after losing one unit.

Limitation: very long weak ties may create inter-area oscillations and a fault can cascade, so a grid is more stable only when it is properly planned, protected and controlled.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Transmission and Distribution System Design chapter 1 questions →