Short answer

SSR is the ratio of peak switching surge voltage to peak normal phase voltage. With closing resistors and synchronized switching, the practical minimum is about 1.8–2.0; reducing it further is uneconomical and gives little insulation saving, so values below 1.8 are not chosen.

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: The value of SSR should not be chosen below 1.8.

TRUE (as a practical design rule).

  • SSR is the ratio of peak switching surge voltage to peak normal phase voltage. Switching a line always produces some transient over-voltage due to trapped charge, travelling-wave reflection and the Ferranti rise.
  • With closing resistors, synchronised (point-on-wave) switching and metal-oxide arresters the SSR can be reduced to about 1.8–2.0 pu; reducing it further needs very costly equipment and gives little saving in insulation.
  • Temporary over-voltages and arrester protective level also set a lower bound: the insulation must anyway withstand arrester residual voltage plus margin.

Hence in design an SSR below about 1.8 is not chosen; values of 1.8–2.0 are used for UHV and higher values for lower voltages.