T/F: SSR not below 1.8
Short answer
SSR is the ratio of peak switching surge voltage to peak normal phase voltage. With closing resistors and synchronized switching, the practical minimum is about 1.8–2.0; reducing it further is uneconomical and gives little insulation saving, so values below 1.8 are not chosen.
State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: The value of SSR should not be chosen below 1.8.
TRUE (as a practical design rule).
- SSR is the ratio of peak switching surge voltage to peak normal phase voltage. Switching a line always produces some transient over-voltage due to trapped charge, travelling-wave reflection and the Ferranti rise.
- With closing resistors, synchronised (point-on-wave) switching and metal-oxide arresters the SSR can be reduced to about 1.8–2.0 pu; reducing it further needs very costly equipment and gives little saving in insulation.
- Temporary over-voltages and arrester protective level also set a lower bound: the insulation must anyway withstand arrester residual voltage plus margin.
Hence in design an SSR below about 1.8 is not chosen; values of 1.8–2.0 are used for UHV and higher values for lower voltages.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: switching surge ratio vs system voltage · Transmission and Distribution System Design, chapter 3 · asked 4×
- T/F: earth wire choice depends on circuit and voltage · Transmission and Distribution System Design, chapter 3
- T/F: span choice depends on voltage only · Transmission and Distribution System Design, chapter 4
- T/F: flashover voltage vs puncture voltage · Transmission and Distribution System Design, chapter 3 · asked 3×
- T/F: ampacity vs ambient temperature · Transmission and Distribution System Design, chapter 4 · asked 2×
- T/F: tower height independent of span · Transmission and Distribution System Design, chapter 4 · asked 2×
- CT secondary should not be kept open · Electrical Machines, chapter 2
- True/false: CT secondary kept open · Electrical Machine, chapter 2
- True/false: derivative controllers always used with others · Control Systems, chapter 7 · asked 3×
- True/false: series motor started at no load · Electrical Machine, chapter 4
All Transmission and Distribution System Design chapter 3 questions →