T/F: thermal limit design urban, losses rural
Short answer
TRUE. Urban feeders carry large currents over short lengths, so thermal (ampacity) is the design limit. Rural feeders are very long with small loads, designed by voltage drop. Their high resistance due to length, low load factor, and unbalanced loading cause higher percentage power loss than in urban feeders.
State and justify whether the following statement is TRUE or FALSE: Though thermal limit design for distribution feeder is applicable in highly dense urban areas, but the power loss are more in rural areas.
TRUE.
Thermal limit in urban areas:
- Urban areas have high load density (many kW per km²), so feeders are short but carry large currents.
- Over a short length, the voltage drop () stays within limits even at high current. The limiting factor is the current-carrying (thermal) capacity of the conductor or cable: overheating, sag and insulation damage.
- So urban feeders are designed by the thermal (ampacity) limit.
Higher losses in rural areas:
- Rural loads are scattered, with low load density, so feeders (11 kV and LT) are very long for small loads. They are designed by the voltage drop limit, not the thermal limit.
- Power loss , and is proportional to length. For the same delivered power, long feeders with small conductors give a much higher percentage loss.
- Rural distribution transformers are lightly loaded for most of the day (low load factor), so no-load (core) losses form a large share of the energy supplied.
- Poor maintenance, unbalanced single-phase loading, long service drops and theft add to the losses.
Example: a 10 kW load at the end of a 0.5 km LT feeder has only one-quarter of the loss of the same load at the end of a 2 km feeder (loss ∝ length for a fixed current).
Thus urban feeders reach their thermal limit first, while rural feeders, though lightly loaded, have a higher percentage loss than urban feeders.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Underground feeder economical in urban areas · Transmission and Distribution System Design, chapter 5 · asked 4×
- T/F: 765 kV stability limit vs thermal limit · Transmission and Distribution System Design, chapter 2
- T/F: higher primary voltage in rural distribution · Transmission and Distribution System Design, chapter 7 · asked 2×
- T/F: loop arrangement in urban area economical · Transmission and Distribution System Design, chapter 5
- T/F: urban design, transformer location first · Transmission and Distribution System Design, chapter 7
- Justify higher voltage/more circuits for more power · Transmission and Distribution System Design, chapter 2
- True/false: rotor core loss neglected · Electrical Machine, chapter 5
- True/False: ampere conductors and temperature rise · Electric Machine Design, chapter 5
- True/False: armature reaction and ampere conductors · Electric Machine Design, chapter 5
- True/False: air gap length and cost · Electric Machine Design, chapter 5
All Transmission and Distribution System Design chapter 7 questions →