- 2072 Magh · 3 marks
T/F: 765 kV stability limit vs thermal limit
Short answer
FALSE. For a 765 kV line the transient stability limit is less than the thermal limit because EHV lines are long and stability-limited; thermal capacity is very high (4000–6000 MW) while stability limit is only about 1–1.5 × SIL (around 2250–3375 MW).
State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: For a 765 kV line transient stability limit is more than the thermal limit.
FALSE. For a 765 kV line the transient stability limit is less than the thermal limit (for practical line lengths).
- Thermal limit depends on conductor area; a 765 kV line uses 4–6 sub-conductor bundles, so its thermal capacity is very large (about 4000–6000 MW, i.e. 2–3 × SIL).
- The SIL of a 765 kV line is about MW. Because EHV lines are long (300–600 km), the power limited by stability/voltage drop is only about 1–1.5 × SIL.
- Hence in EHV/UHV lines power transfer is stability-limited, not thermally limited; only short lines (< 80 km) are thermally limited.
That is why series compensation and FACTS are used on such lines: they raise the stability limit toward the thermal limit.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: radial more reliable than network · Transmission and Distribution System Design, chapter 5 · asked 2×
- T/F: thermal limit design urban, losses rural · Transmission and Distribution System Design, chapter 7 · asked 3×
- T/F: more circuits rather than higher voltage · Transmission and Distribution System Design, chapter 2
- T/F: temporary vs transient overvoltage · Transmission and Distribution System Design, chapter 3
- T/F: stability criterion implies thermal criterion · Transmission and Distribution System Design, chapter 4 · asked 2×
- T/F: grid connected system more stable · Transmission and Distribution System Design, chapter 1
- Check corona on 765 kV line · High Voltage Engineering, chapter 5
- True/false: derivative controllers always used with others · Control Systems, chapter 7 · asked 3×
- Audible noise of 765 kV line (18 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 765 kV line (18.4 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
All Transmission and Distribution System Design chapter 2 questions →