T/F: stability criterion implies thermal criterion
Short answer
TRUE. On long lines (above about 320 km), the steady-state stability limit is much smaller than thermal rating because reactance grows with length. If the stability criterion is satisfied, the current is well below the conductor's ampacity, so the thermal criterion is automatically met.
State and justify whether the following statement is TRUE or FALSE: While designing the long transmission line, if the stability criterion is met then the thermal criterion is also met.
TRUE (for long lines).
The power a line can carry is limited by three criteria (St. Clair loadability curve):
| Line length | Governing limit | Typical loadability |
|---|---|---|
| Short (up to about 80 km) | Thermal | about 3 × SIL |
| Medium (80–320 km) | Voltage drop (about 5%) | 1.5–3 × SIL |
| Long (above 320 km) | Steady-state stability | about 1 × SIL or less |
The stability limit (with kept to about 30°–35°) falls as the line length increases, because grows with length. The thermal limit does not depend on length.
For a long line, the stability-limited power is therefore much smaller than the thermal capacity of the chosen conductor. If the line is designed so that the stability criterion is met, the current is well below the conductor's ampacity, so the thermal criterion is automatically met.
The converse is not true. A long line that meets the thermal criterion may still fail the stability criterion.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: 765 kV stability limit vs thermal limit · Transmission and Distribution System Design, chapter 2
- T/F: X/R ratio, transmission vs distribution · Transmission and Distribution System Design, chapter 1
- T/F: thermal limit design urban, losses rural · Transmission and Distribution System Design, chapter 7 · asked 3×
- T/F: power transfer capability vs line length · Transmission and Distribution System Design, chapter 2 · asked 2×
- Justify higher voltage/more circuits for more power · Transmission and Distribution System Design, chapter 2
- Justify: trending method for large area forecast · Transmission and Distribution System Design, chapter 6
- True/false: CT secondary kept open · Electrical Machine, chapter 2
- True/false: derivative controllers always used with others · Control Systems, chapter 7 · asked 3×
- True/false: series motor started at no load · Electrical Machine, chapter 4
- True/false: rotor core loss neglected · Electrical Machine, chapter 5
All Transmission and Distribution System Design chapter 4 questions →