Justify the two wattmeter method

Short answer

In a three-wire system, iR+iY+iB=0, so instantaneous power p = (vR-vY)iR + (vB-vY)iB = vRY iR + vBY iB. Two wattmeters with current coils in lines R and B and pressure coils to Y read the averages of these terms, their sum gives total three-phase power, valid for unbalanced loads without neutral.

Justify the use of two wattmeter to calculate the power of 3 φ load.

Statement: The power of a three-wire three-phase load can be measured with two wattmeters, because the sum of their readings equals the total power.

Justification

Connect the current coils of the two wattmeters in lines R and B, and join both pressure coils to the third line Y.

Total instantaneous power: p = v_R i_R + v_Y i_Y + v_B i_B

Since i_R + i_Y + i_B = 0 (three-wire system), i_Y = −(i_R + i_B), so

p = (v_R − v_Y) i_R + (v_B − v_Y) i_B = v_RY i_R + v_BY i_B

  • W₁ reads the mean of v_BY i_B
  • W₂ reads the mean of v_RY i_R

Hence P = W₁ + W₂. This is true for star or delta and for balanced or unbalanced loads.

For a balanced load with lagging angle φ:

  • W₁ = V_L I_L cos(30° − φ)
  • W₂ = V_L I_L cos(30° + φ)

W₁ + W₂ = V_L I_L × 2 cos 30° cos φ = √3 V_L I_L cos φ, the total three-phase power.

Two wattmeters are used instead of three because the neutral point does not need to be accessible (so it works for delta loads and for star loads without a neutral), and one meter is saved. For a balanced load it also gives the power factor: tan φ = √3 (W₁ − W₂)/(W₁ + W₂).