Two wattmeter method connection diagram
Short answer
Current coils are placed in lines R and B, with pressure coils connected between their own lines and the third line Y. The sum of readings gives total three-phase power: W1 = V_L I_L cos(30°–φ), W2 = V_L I_L cos(30°+φ), and P = W1+W2 = √3 V_L I_L cos φ, while tan φ = √3 (W1–W2)/(W1+W2).
Explain with connection diagram the measurement of 3-φ power using two wattmeters.
Principle: The total power in a three-wire three-phase circuit (star or delta, balanced or unbalanced) can be measured with two wattmeters. The algebraic sum of their readings is the total power.
Connection diagram
R ──[ W2: CC ]───────────┬──► load
PC ──────┐ │
Y ──────────────┴────────┼──► load
PC ──────┐ │
B ──[ W1: CC ]───────────┴──► load
- The current coils (CC) are in series with two of the lines (R and B).
- One end of each pressure coil (PC) is connected to the line of its own current coil, and the other ends of both are joined to the third line (Y).
- Each wattmeter measures the average of (line-to-Y voltage) × (current in its own line).
Readings (balanced load, lagging power factor cos φ)
- W₁ = V_L I_L cos(30° − φ)
- W₂ = V_L I_L cos(30° + φ)
Total power P = W₁ + W₂ = √3 V_L I_L cos φ
Also: tan φ = √3 (W₁ − W₂)/(W₁ + W₂), so the power factor of the load can be found from the readings. Reactive power Q = √3 (W₁ − W₂).
Notes
- At unity power factor both wattmeters read the same.
- At cos φ = 0.5, one wattmeter reads zero and the other reads the total power.
- For cos φ < 0.5, one wattmeter reads negative. Its pressure-coil connection is reversed to get a deflection, and that reading is subtracted.
- It cannot be used for a four-wire system with a neutral current, where three wattmeters are needed.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Two wattmeter method proof · Basic Electrical Engineering, chapter 8 · asked 3×
- Two wattmeter method for unbalanced load · Basic Electrical Engineering, chapter 8
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Justify the two wattmeter method · Basic Electrical Engineering, chapter 8
- Reactive power and power phasor diagram · Basic Electrical Engineering, chapter 7
- Power ratio of two resistors at 70°C · Basic Electrical Engineering, chapter 1
- Two-wattmeter method star load · Basic Electrical and Electronics Engineering, chapter 1
- Series connection of two full converters · Power Electronics, chapter 2 · asked 2×
- Scott connection for three-phase to two-phase · Electrical Machines I, chapter 2
- Series connection of two-port networks · Filter Design, chapter 4