Two wattmeter method proof
Short answer
In a three-wire system, instantaneous power p = v_RY i_R + v_BY i_B. Two wattmeters measure the averages of these products, so total power P = W1 + W2. For balanced load, W1 = V_L I_L cos(30°–φ), W2 = V_L I_L cos(30°+φ), sum = √3 V_L I_L cos φ.
Prove that sum of the readings of two wattmeters is equal to the total three phase power in measurement of power of 3-phase circuit by 2 wattmeter method.
Statement: In a three-wire three-phase system, the sum of the readings of two wattmeters equals the total power consumed, for a balanced or an unbalanced load.
Connection
The current coil (CC) of W₁ is in line B and that of W₂ in line R. The pressure coils (PC) of both are connected to line Y, the common line.
R ──[ W2: CC ]───────────┬── load
PC ──────┐ │
Y ──────────────┴────────┼── load
PC ──────┐ │
B ──[ W1: CC ]───────────┴── load
General proof
Instantaneous power of a star-connected load (or its star equivalent):
p = v_R i_R + v_Y i_Y + v_B i_B
For a three-wire system i_R + i_Y + i_B = 0, so i_Y = −(i_R + i_B). Substituting:
p = v_R i_R + v_B i_B − v_Y (i_R + i_B) = (v_R − v_Y) i_R + (v_B − v_Y) i_B = v_RY i_R + v_BY i_B
- W₂ reads the average of v_RY i_R
- W₁ reads the average of v_BY i_B
So the total power is P = W₁ + W₂.
Balanced load: phasor proof
Take RYB sequence with V_RN = V_ph∠0°, V_YN = V_ph∠−120°, V_BN = V_ph∠120°. The load current lags its phase voltage by φ. Let V_L be the line voltage and I_L the line current.
- V_RY = V_RN − V_YN = V_L∠30°; I_R = I_L∠−φ. Angle between them = 30° + φ. W₂ = V_L I_L cos(30° + φ)
- V_BY = V_BN − V_YN = V_L∠90°; I_B = I_L∠(120° − φ). Angle between them = 30° − φ. W₁ = V_L I_L cos(30° − φ)
Sum:
W₁ + W₂ = V_L I_L [cos(30° − φ) + cos(30° + φ)] = V_L I_L × 2 cos 30° cos φ = V_L I_L × 2 × (√3/2) × cos φ = √3 V_L I_L cos φ
This is the total three-phase power. Hence proved.
Further results
- W₁ − W₂ = V_L I_L [cos(30° − φ) − cos(30° + φ)] = V_L I_L sin φ
- tan φ = √3 (W₁ − W₂)/(W₁ + W₂)
- At unity pf (φ = 0) both read equal. At pf 0.5 (φ = 60°) W₂ = 0. For pf below 0.5, W₂ reads negative.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Two wattmeter method for unbalanced load · Basic Electrical Engineering, chapter 8
- Total power of series-parallel circuit · Basic Electrical Engineering, chapter 6
- Two wattmeter method connection diagram · Basic Electrical Engineering, chapter 8 · asked 2×
- Justify the two wattmeter method · Basic Electrical Engineering, chapter 8
- Combined balanced three-phase loads · Basic Electrical Engineering, chapter 8
- Two isotropic sources, equal amplitude, opposite phase · Propagation and Antenna, chapter 2 · asked 3×
- Two-wattmeter method star load · Basic Electrical and Electronics Engineering, chapter 1
- Induction motor equivalent circuit from two-wattmeter tests · Electrical Machines I, chapter 5
- Scott connection for three-phase to two-phase · Electrical Machines I, chapter 2