- Practice · 6 marks
Basic psychrometric processes
Short answer
Sensible heating/cooling holds ω constant, moving horizontally; Q = ṁₐ(h₂−h₁). Cooling and dehumidification occurs below dew point with moisture removal, Q = ṁₐ(h₁−h₂) − ṁ_w h_w, ṁ_w = ṁₐ(ω₁−ω₂). Heating and humidification adds moisture: ṁ_w = ṁₐ(ω₂−ω₁), Q = ṁₐ(h₂−h₁) − ṁ_w h_w.
Explain the following psychrometric processes with sketches on the psychrometric chart and give the energy equations: (a) sensible heating, (b) sensible cooling, (c) cooling and dehumidification, (d) heating and humidification.
Let be the mass flow of dry air, and 1 and 2 the inlet and outlet states.
(a) Sensible heating
Heat is added with no change in . The state moves horizontally to the right; DBT, WBT and enthalpy rise, RH falls.
with humid specific heat kJ/kg K. Done by an electric or steam heating coil.
(b) Sensible cooling
Air is cooled by a coil whose surface temperature is above the dew point, so stays constant. The state moves horizontally to the left; RH rises. The same equation applies with the sign reversed.
(c) Cooling and dehumidification
The coil surface is below the dew point of the entering air, so vapour condenses. The state moves down and to the left.
The load splits into sensible and latent parts, . This is the main summer air-conditioning process.
(d) Heating and humidification
Used in winter: air is heated, then water or steam is added. Specific humidity and temperature both rise.
w ^
| o 2d (d)
| /
| 2b o<-----o 1 ---->o 2a
| /
| 2c o (c)
+------------------------> DBT
(a) sensible heating, (b) sensible cooling, (c) cooling and dehumidification, (d) heating and humidification.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Construction of the psychrometric chart · Applied Thermodynamics, chapter 4
- Sensible heating of air numerical · Applied Thermodynamics, chapter 4
- Cooling and dehumidifying coil load · Applied Thermodynamics, chapter 4
- Heating and cooling time constants · Electric Machine Design, chapter 2 · asked 3×
- Transformer heating and cooling time constants (25°C/37.5°C) · Electric Machine Design, chapter 2 · asked 3×
- Transformer heating and cooling time constants (25°C/40°C) · Electric Machine Design, chapter 2 · asked 3×
- Air: PV^3 expansion, cooling, heating; total work · Fundamental of Thermodynamics & Heat Transfer, chapter 2