Transformer heating and cooling time constants (25°C/37.5°C)

Short answer

From rises: 25°C at 1 h, 37.5°C at 2 h, solve 1 + e^(-1/tau_h) = 1.5 → e^(-1/tau_h)=0.5 → theta_m=50°C, heating time constant 1.443 h. Cooling: from 80°C to 40°C in 2.5 h with ambient 30°C gives 10 = 50 e^(-2.5/tau_c) → cooling time constant 1.553 h.

The temperature rise of a transformer is 25°C after one hour and 37.5°C after two hours of starting from cold conditions. Calculate the final steady state temperature rise and the heating time constant. If its temperature falls from the final steady value to 40°C in 2.5 hours when disconnected, calculate its cooling time constant. The ambient temperature is 30°C.

Given

  • Temperature rise from cold: θ1=25\theta_1 = 25 °C at t=1t = 1 h, θ2=37.5\theta_2 = 37.5 °C at t=2t = 2 h
  • On disconnection, the temperature falls from its final steady value to 40 °C in 2.5 h; ambient = 30 °C.

Heating: final rise and heating time constant

From cold, θ=θm(1−e−t/τh)\theta = \theta_m(1 - e^{-t/\tau_h}). Let a=e−1/τha = e^{-1/\tau_h}:

25=θm(1−a)37.5=θm(1−a2)=θm(1−a)(1+a)\begin{aligned} 25 &= \theta_m(1 - a) \\ 37.5 &= \theta_m(1 - a^2) = \theta_m(1-a)(1+a) \end{aligned}

Dividing:

1+a=37.525=1.5  ⇒  a=0.5θm=251−0.5=50 ∘Cτh=1ln⁡(1/a)=1ln⁡2=1.443 h≈86.6 min\begin{aligned} 1 + a &= \frac{37.5}{25} = 1.5 \;\Rightarrow\; a = 0.5 \\ \theta_m &= \frac{25}{1 - 0.5} = 50\ ^\circ\text{C} \\ \tau_h &= \frac{1}{\ln(1/a)} = \frac{1}{\ln 2} = 1.443\ \text{h} \approx 86.6\ \text{min} \end{aligned}

Cooling time constant

Final steady temperature = 30 + 50 = 80 °C (rise 50 °C). After 2.5 h the temperature is 40 °C, i.e. a rise of 40 − 30 = 10 °C above ambient.

θ=θi e−t/τc10=50 e−2.5/τcτc=2.5ln⁡(50/10)=2.5ln⁡5=2.51.6094=1.553 h≈93.2 min\begin{aligned} \theta &= \theta_i\, e^{-t/\tau_c} \\ 10 &= 50\, e^{-2.5/\tau_c} \\ \tau_c &= \frac{2.5}{\ln(50/10)} = \frac{2.5}{\ln 5} = \frac{2.5}{1.6094} = 1.553\ \text{h} \approx 93.2\ \text{min} \end{aligned}

Answer: final steady temperature rise = 50 °C; heating time constant = 1.443 h (86.6 min); cooling time constant = 1.553 h (93.2 min).

The cooling time constant is larger than the heating one, as expected, because heat dissipation is poorer when the transformer is not loaded (weaker oil circulation).

✓ Answer checked by Claude Sonnet 5.5