Heating constant and 1-hour rating (400 kVA)

Short answer

Oil rises: 24°C at 1.5h, 36°C at 3h (ambient 35°C). x=e^(-1.5/τ)=0.5 → τ=2.164h, θm=48°C. 1-hour rating: 48=θm'(1-e^(-1/2.164)) → θm'=129.72°C. Pc=2Pi, full-load losses 3Pi; losses ratio 129.72/48 gives k²=3.554, k=1.885, rating 754kVA. τ=2.164h, final rise 48°C, 1-hour rating 754kVA.

A 400 kVA 1100/400V three phase transformer is working in an ambient temperature of 35°C on full load, its oil temperature is recorded as follows: 59°C after 1.5 hour and 71°C after 3 hours. Its full load copper losses is 2 times the iron losses. Calculate its heating time constant, final steady temperature rise and 1 hour rating.

Temperature rise above ambient (35 °C):

  • after 1.5 h: θ1=59−35=24 ∘\theta_1 = 59 - 35 = 24\ ^\circC
  • after 3 h: θ2=71−35=36 ∘\theta_2 = 71 - 35 = 36\ ^\circC

Heating from cold: θ=θm(1−e−t/τ)\theta = \theta_m(1-e^{-t/\tau}).

i) Heating time constant

Let x=e−1.5/τx = e^{-1.5/\tau}. Since 3 h = 2 × 1.5 h:

θ2θ1=1−x21−x=1+x=3624=1.5  ⇒  x=0.5τ=1.5ln⁡2=2.164 h\begin{aligned} \frac{\theta_2}{\theta_1} &= \frac{1-x^2}{1-x} = 1 + x = \frac{36}{24} = 1.5 \;\Rightarrow\; x = 0.5\\ \tau &= \frac{1.5}{\ln 2} = 2.164\ \text{h} \end{aligned}

ii) Final steady temperature rise

θm=241−0.5=48 ∘C\theta_m = \frac{24}{1-0.5} = 48\ ^\circ\text{C}

(Final oil temperature = 35 + 48 = 83 °C.)

iii) One-hour rating

The 1-hour rating is the load that, starting cold, brings the rise to 48 °C in exactly 1 hour. Let its final rise be θm′\theta_m':

48=θm′(1−e−1/2.164)=θm′(1−0.630)=0.370 θm′θm′=129.72 ∘C\begin{aligned} 48 &= \theta_m'\left(1-e^{-1/2.164}\right) = \theta_m'(1-0.630) = 0.370\,\theta_m'\\ \theta_m' &= 129.72\ ^\circ\text{C} \end{aligned}

Final rise ∝ losses. With Pc=2PiP_c = 2P_i at full load, losses at load fraction kk are Pi(1+2k2)P_i(1+2k^2), and at full load 3Pi3P_i:

1+2k23=129.7248=2.702k2=3(2.702)−12=3.554  ⇒  k=1.885\begin{aligned} \frac{1+2k^2}{3} &= \frac{129.72}{48} = 2.702\\ k^2 &= \frac{3(2.702)-1}{2} = 3.554 \;\Rightarrow\; k = 1.885 \end{aligned}

One-hour rating =1.885×400=754= 1.885 \times 400 = 754 kVA.

Answer: τ\tau = 2.164 h, final steady rise = 48 °C, 1-hour rating ≈ 754 kVA (1.885 × full load).