- 2082 Chaitra (new course) · 4 marks
Heating constant and 1-hour rating (40 kVA)
Short answer
Heating time constant τ = 1.5/ln 2 ≈ 2.164 h. Final steady temperature rise is 48 °C. For a 1‑hour rating the required final rise is 129.72 °C; using loss ratio (1+2k²)/3 = 129.72/48 gives k = 1.885, so rating = 75.4 kVA.
A 40 kVA, 11000/400 V, 3-phase transformer is working in an ambient temperature of 35°C on full load. Its oil temperature is recorded as follows: 59°C after 1.5 hours; 71°C after 3 hours. Its full-load copper losses are 2 times the iron losses. Calculate: i) Heating time constant ii) Final steady temperature rise iii) 1-hour rating
Temperature rise above ambient (35 °C):
- after 1.5 h: C
- after 3 h: C
Heating from cold: .
i) Heating time constant
Let . Since 3 h = 2 × 1.5 h:
ii) Final steady temperature rise
(Final oil temperature = 35 + 48 = 83 °C.)
iii) One-hour rating
The 1-hour rating is the load that, starting cold, brings the rise to 48 °C in exactly 1 hour. Let its final rise be :
Final rise ∝ losses. With at full load, losses at load fraction are , and at full load :
One-hour rating kVA.
Answer: = 2.164 h, final steady rise = 48 °C, 1-hour rating ≈ 75.4 kVA (1.885 × full load).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Heating constant and 1-hour rating (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Machine temperature after one hour of heating · Electric Machine Design, chapter 2
- New kVA rating with fan cooling (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Transformer heating and cooling time constants (25°C/40°C) · Electric Machine Design, chapter 2 · asked 3×
- Temperature rise and tubes for 500 kVA transformer · Electric Machine Design, chapter 3 · asked 2×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×