New kVA rating with fan cooling (150 kVA)

Short answer

Rises 25°C at 1h and 37.5°C at 2h give a=0.5, τ=1.443h (86.6min), θm=50°C. Max eff at 80% → Pi=0.64Pc, full-load losses 1.64Pc. 20% better dissipation allows 1.2×1.64=1.968 times Pc; solving 0.64+x²=1.968 → x=1.1524, new rating 172.9kVA. Heating time constant 1.443h, final steady rise 50°C, new kVA 172.9kVA.

The temperature rise of a 150 kVA transformer is 25°C and 37.5°C after 1 and 2 hours respectively starting from cold condition. Calculate its heating time constant and final steady temperature rise. If the rate of heat dissipation is improved by 20% with help of external fan, find the new kVA rating for same steady temperature rise. The maximum efficiency occurs at 80% of full load.

Given

  • 150 kVA; temperature rise from cold: 25 °C after 1 h, 37.5 °C after 2 h
  • Fan improves heat dissipation by 20 %; maximum efficiency at 80 % of full load

Step 1: time constant and final rise

With a=e−1/τa = e^{-1/\tau}:

1+a=37.525=1.5  ⇒  a=0.5τ=1ln⁡2=1.443 h≈86.6 minθm=251−0.5=50 ∘C\begin{aligned} 1 + a &= \frac{37.5}{25} = 1.5 \;\Rightarrow\; a = 0.5 \\ \tau &= \frac{1}{\ln 2} = 1.443\ \text{h} \approx 86.6\ \text{min} \\ \theta_m &= \frac{25}{1 - 0.5} = 50\ ^\circ\text{C} \end{aligned}

Step 2: losses

At maximum efficiency (80 % load), iron loss = copper loss at that load:

Pi=0.82Pc=0.64 PcFull-load losses=0.64Pc+Pc=1.64 Pc\begin{aligned} P_i &= 0.8^2 P_c = 0.64\,P_c \\ \text{Full-load losses} &= 0.64P_c + P_c = 1.64\,P_c \end{aligned}

Step 3: new rating for the same final rise

Since θm=lossesSλ\theta_m = \dfrac{\text{losses}}{S\lambda}, a 20 % higher λ\lambda allows 20 % more losses for the same θm\theta_m. At xx times the old full load:

0.64+x2=1.2×1.64=1.968x2=1.328  ⇒  x=1.1524New rating=1.1524×150=172.9 kVA\begin{aligned} 0.64 + x^2 &= 1.2 \times 1.64 = 1.968 \\ x^2 &= 1.328 \;\Rightarrow\; x = 1.1524 \\ \text{New rating} &= 1.1524 \times 150 = 172.9\ \text{kVA} \end{aligned}

Answer: heating time constant = 1.443 h (86.6 min); final steady rise = 50 °C; new rating with fan ≈ 172.9 kVA.