New kVA rating with fan cooling (350 kVA)

Short answer

Using 24°C at 1h and 34°C at 2h: a=0.4167, τ=1.14h (68.5min), θm=41.14°C. Pi=0.7225Pc, full-load losses 1.7225Pc. With 15% better cooling: same rise allows 1.15×losses → rating 392.6kVA; 50°C rise gives 1.15×50/41.14×losses → 454.3kVA. So τ≈1.14h, final rise≈41.1°C; new ratings (i)393kVA, (ii)454kVA.

A 350 kVA transformer has its maximum efficiency at 85% of full load. During a short full load heat run the temperature rise after one hour and two hours is observed to be 24°C and 34°C respectively. Find thermal time constant and final steady temperature rise of the transformer. If by use of fan, cooling is improved so that heat dissipation per unit area per degree rise in temperature is increased by 15%, find the new kVA rating possible (i) for same final temperature rise as before (ii) if the allowable temperature rise is taken as 50°C.

Given

  • Rating SS = 350 kVA; maximum efficiency at 85 % of full load
  • Heat run at full load: θ1=24\theta_1 = 24 °C after 1 h, θ2=34\theta_2 = 34 °C after 2 h
  • Fan cooling raises heat dissipation per unit area per °C (λ\lambda) by 15 %

Step 1: time constant and final temperature rise

With a=e−1/τa = e^{-1/\tau}, θ1=θm(1−a)\theta_1 = \theta_m(1-a) and θ2=θm(1−a2)\theta_2 = \theta_m(1-a^2):

1+a=3424=1.4167  ⇒  a=0.4167τ=1ln⁡(1/0.4167)=1ln⁡2.4=1.142 h≈68.5 minθm=241−0.4167=41.14 ∘C\begin{aligned} 1 + a &= \frac{34}{24} = 1.4167 \;\Rightarrow\; a = 0.4167 \\ \tau &= \frac{1}{\ln(1/0.4167)} = \frac{1}{\ln 2.4} = 1.142\ \text{h} \approx 68.5\ \text{min} \\ \theta_m &= \frac{24}{1 - 0.4167} = 41.14\ ^\circ\text{C} \end{aligned}

Step 2: losses in terms of full-load copper loss PcP_c

At maximum efficiency, copper loss = iron loss:

Pi=(0.85)2Pc=0.7225 PcFull-load losses=Pi+Pc=1.7225 Pc\begin{aligned} P_i &= (0.85)^2 P_c = 0.7225\,P_c \\ \text{Full-load losses} &= P_i + P_c = 1.7225\,P_c \end{aligned}

The final rise is θm=lossesSλ\theta_m = \dfrac{\text{losses}}{S\lambda}, so the losses allowed ∝λ θm\propto \lambda\,\theta_m. At a new load of xx times full load, the losses are Pi+x2PcP_i + x^2 P_c (iron loss is constant).

(i) Same final temperature rise (41.1441.14 °C)

Losses allowed rise by 15 %:

0.7225+x2=1.15×1.7225=1.9809x2=1.2584  ⇒  x=1.1218New rating=1.1218×350=392.6 kVA\begin{aligned} 0.7225 + x^2 &= 1.15 \times 1.7225 = 1.9809 \\ x^2 &= 1.2584 \;\Rightarrow\; x = 1.1218 \\ \text{New rating} &= 1.1218 \times 350 = 392.6\ \text{kVA} \end{aligned}

(ii) Allowable temperature rise 50 °C

Losses allowed are now in the ratio 1.15×5041.141.15 \times \dfrac{50}{41.14}:

0.7225+x2=1.15×5041.14×1.7225=2.4073x2=1.6848  ⇒  x=1.2980New rating=1.2980×350=454.3 kVA\begin{aligned} 0.7225 + x^2 &= 1.15 \times \frac{50}{41.14} \times 1.7225 = 2.4073 \\ x^2 &= 1.6848 \;\Rightarrow\; x = 1.2980 \\ \text{New rating} &= 1.2980 \times 350 = 454.3\ \text{kVA} \end{aligned}

Answer: time constant ≈ 1.14 h (68.5 min); final rise ≈ 41.1 °C; new rating (i) ≈ 393 kVA, (ii) ≈ 454 kVA.