New kVA rating with fan cooling (350 kVA)
Short answer
Using 24°C at 1h and 34°C at 2h: a=0.4167, τ=1.14h (68.5min), θm=41.14°C. Pi=0.7225Pc, full-load losses 1.7225Pc. With 15% better cooling: same rise allows 1.15×losses → rating 392.6kVA; 50°C rise gives 1.15×50/41.14×losses → 454.3kVA. So τ≈1.14h, final rise≈41.1°C; new ratings (i)393kVA, (ii)454kVA.
A 350 kVA transformer has its maximum efficiency at 85% of full load. During a short full load heat run the temperature rise after one hour and two hours is observed to be 24°C and 34°C respectively. Find thermal time constant and final steady temperature rise of the transformer. If by use of fan, cooling is improved so that heat dissipation per unit area per degree rise in temperature is increased by 15%, find the new kVA rating possible (i) for same final temperature rise as before (ii) if the allowable temperature rise is taken as 50°C.
Given
- Rating = 350 kVA; maximum efficiency at 85 % of full load
- Heat run at full load: °C after 1 h, °C after 2 h
- Fan cooling raises heat dissipation per unit area per °C () by 15 %
Step 1: time constant and final temperature rise
With , and :
Step 2: losses in terms of full-load copper loss
At maximum efficiency, copper loss = iron loss:
The final rise is , so the losses allowed . At a new load of times full load, the losses are (iron loss is constant).
(i) Same final temperature rise ( °C)
Losses allowed rise by 15 %:
(ii) Allowable temperature rise 50 °C
Losses allowed are now in the ratio :
Answer: time constant ≈ 1.14 h (68.5 min); final rise ≈ 41.1 °C; new rating (i) ≈ 393 kVA, (ii) ≈ 454 kVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- New kVA rating with fan cooling (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- New kVA rating with fan cooling (150 kVA) · Electric Machine Design, chapter 2
- Full-load heat run and 50% overload time · Electric Machine Design, chapter 2
- Heating constant and 1-hour rating (400 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Heating constant and 1-hour rating (40 kVA) · Electric Machine Design, chapter 2 · asked 2×
- Machine temperature after one hour of heating · Electric Machine Design, chapter 2
- Temperature rise and tubes for 500 kVA transformer · Electric Machine Design, chapter 3 · asked 2×
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2