Full-load rises 20°C (1h) and 32°C (2h): a=0.6, τ=1.958h, θm=50°C. Copper loss = 2× iron loss, so full-load losses = 3Pi, 50% overload losses = 5.5Pi, overload final rise 91.67°C. Time to 50°C: 50=91.67(1-e^(-t/1.958)) → t=1.543h (92.6min). Final steady rise 50°C, time on 50% overload ≈1.54h.

A transformer has a temperature rise of 20°C after one hour and 32°C after two hours on full load. What is the final steady state temperature rise at full load? If the transformer is working on 50% over load, how long will it take to attain the same temperature rise? Take the copper losses on full load equal to twice the iron loss.

Heating from cold follows θ=θm(1−e−t/τ)\theta = \theta_m\left(1-e^{-t/\tau}\right). Final rise is proportional to total losses.

Time constant and final steady rise at full load

Let x=e−1/τx = e^{-1/\tau} (τ\tau in hours).

20=θm(1−x),32=θm(1−x2)=θm(1−x)(1+x)3220=1+x  ⇒  x=0.6τ=1ln⁡(1/0.6)=1.958 hθm=201−0.6=50 ∘C\begin{aligned} 20 &= \theta_m(1-x), \qquad 32 = \theta_m(1-x^2) = \theta_m(1-x)(1+x)\\ \frac{32}{20} &= 1 + x \;\Rightarrow\; x = 0.6\\ \tau &= \frac{1}{\ln(1/0.6)} = 1.958\ \text{h}\\ \theta_m &= \frac{20}{1-0.6} = 50\ ^\circ\text{C} \end{aligned}

Losses

Full-load copper loss Pc=2PiP_c = 2P_i.

  • Full load: Pi+2Pi=3PiP_i + 2P_i = 3P_i
  • 50% overload: Pi+(1.5)2(2Pi)=5.5PiP_i + (1.5)^2(2P_i) = 5.5P_i

Final rise on overload:

θmo=50×5.53=91.67 ∘C\theta_{mo} = 50 \times \frac{5.5}{3} = 91.67\ ^\circ\text{C}

Time to reach 50 °C on 50% overload

50=91.67(1−e−t/1.958)e−t/1.958=1−5091.67=0.4545t=1.958ln⁡10.4545=1.543 h\begin{aligned} 50 &= 91.67\left(1-e^{-t/1.958}\right)\\ e^{-t/1.958} &= 1-\frac{50}{91.67} = 0.4545\\ t &= 1.958\ln\frac{1}{0.4545} = 1.543\ \text{h} \end{aligned}

Answer: final steady rise at full load = 50 °C (τ\tau = 1.958 h); on 50% overload the transformer reaches 50 °C in about 1.54 h (≈ 92.6 min).