Copper saving in auto-transformer
Short answer
With ratio K = N2/N1 < 1, the autotransformer copper weight is proportional to 2N1I1(1‑K), compared to 2N1I1 for a two‑winding transformer. The saving is K times the two‑winding copper, i.e., copper saved = K·W2w.
Derive an expression for Cu saving in an auto-transformer.
Consider a single-phase autotransformer with turns across the primary and turns across the secondary (), with
I1 o-->---+ section AB: (N1-N2) turns, current I1
| section BC: N2 turns, current (I2 - I1)
+---o V2, I2 to load
|
o---------+---o
Copper weight is proportional to the length of conductor times its cross-section, which is proportional to turns × current. Hence:
Autotransformer
With and :
Equivalent two-winding transformer
Ratio and saving
The saving is a fraction of the copper of the two-winding transformer. It is large when is near 1 and small when is small.