Short answer
Opening a CT secondary removes opposing mmf, saturates the core, and produces dangerously high voltages. An autotransformer is economical when the ratio K is near unity because copper saving equals K times that of a two-winding transformer (e.g., 90% saving at K=0.9). Applications include motor starters and voltage regulators.
Why secondary of CT should not be left open? Show that auto transformer is economical when the transformation ratio is very close to unity mentioning its application.
Why the secondary of a CT must not be left open
The primary of a CT carries the line current, which is independent of the secondary. With the secondary closed, the mmf nearly cancels , leaving only a small exciting mmf. If the secondary is open, and the whole primary mmf magnetises the core. The flux rises far into saturation, causing very high induced voltage in the many-turn secondary (insulation breakdown and shock hazard), excessive core heating, and residual magnetism that destroys accuracy.
Autotransformer is economical when the ratio is near unity
An autotransformer has a single winding, part of which is common to the primary and the secondary. Let the primary have turns (terminals A–C), the secondary turns (taps B–C), and take . Define .
I1
A o-->------+
| section AB: (N1-N2) turns, current I1
B o---+-----+
| I2-I1 section BC: N2 turns, current (I2 - I1)
C o---+
The amount of copper is proportional to (turns × current) of each winding portion.
Two-winding transformer (primary at , secondary at ):
Autotransformer:
The saving in copper is the fraction of the copper of a two-winding transformer. When is close to 1 (for example 0.9), the autotransformer needs only = 10% of the copper, a saving of 90%. When is small (say 0.2), the saving is only 20%, so it is not economical. Also, only a small part of the power, , is transferred by induction, while the rest is passed directly by conduction, so the core, losses and cost fall in the same way.
Applications: starting of induction motors (autotransformer starter), voltage regulators (variacs), boosting or reducing line voltage by 10 to 20%, and interconnecting 220 kV and 132 kV systems.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CT secondary should not be kept open · Electrical Machines, chapter 2
- Copper saving in auto transformer · Electrical Machines I, chapter 2
- Auto transformer merits and Cu saving · Electrical Machines, chapter 2
- Copper saving in auto-transformer · Electrical Machines, chapter 2
- CT secondary open and PT secondary short · Switchgear and Protection, chapter 2
- True/false: CT secondary kept open · Electrical Machine, chapter 2
- Current transformer vs conventional; CT open · Electrical Machine, chapter 2