Short answer

CT secondary must not be open because primary current becomes magnetizing current, driving core to saturation, producing dangerously high secondary voltage (kV), core overheating, and residual magnetism. PT secondary must not be shorted because fixed primary voltage causes very large short-circuit current limited only by leakage impedance, overheating and burning windings. Safe condition: CT secondary shorted, PT secondary open.

Explain why the secondary of CT should not be left open and secondary of PT should be short circuited.

Why the CT secondary must not be left open

  • A CT primary is in series with the line, so its current I_p is fixed by the load, not by the CT secondary.
  • Normally, secondary ampere-turns N_s·I_s nearly cancel primary ampere-turns; only a small exciting current magnetises the core and the flux density is low.
  • If the secondary is opened, there is no opposing m.m.f. The entire primary current becomes magnetising current, so the flux rises to saturation.
  • Consequences:
    1. Very high secondary voltage: the large secondary turns and rapid flux change (flat-topped flux, steep reversals near current zero) induce peak voltages of several kilovolts. This is dangerous to persons and can break down the secondary insulation.
    2. Core overheating: high flux causes large eddy-current and hysteresis loss, which can burn the insulation.
    3. Residual magnetism: the core may keep remanent flux, increasing future ratio and phase errors.
  • Therefore the CT secondary must always be connected to a burden or short-circuited (using a shorting link or test block) before removing a meter or relay.

Why the PT secondary must not be short-circuited

(The correct practice is that the PT secondary must not be short-circuited.)

  • A PT primary is connected across the line and works like a normal power transformer with a fixed primary voltage; the secondary feeds high-impedance loads and runs almost on open circuit.
  • If the secondary is short-circuited, the only limit to current is the small leakage impedance of the windings, so a very large short-circuit current flows.
  • This overheats and burns the windings within a short time and can damage the PT and cause a fault on the HV side.
  • Hence the PT secondary must be left open (no-load condition is safe) and is protected by fuses or MCBs; the PT primary is also protected by HV fuses.
CTPT
Safe conditionSecondary shortedSecondary open
Dangerous conditionSecondary openSecondary shorted