- 2078 Chaitra · 4 marks
CT with ammeter numerical
Short answer
Using ampere-turns balance: I_s = I_p × N_p/N_s = 900 × 1/180 = 5 A maximum secondary current. With ammeter removed, secondary open-circuit voltage V_s = (400/√3) × 180 ≈ 41.6 kV (phase voltage times turns ratio). This demonstrates why CT secondary must never be opened under load.
A current transformer is connected in 400 V system and has 1 turn on its primary and 180 turns on its secondary. An ammeter with 0.15 Ω internal resistance is connected to CT. The ammeter is required to give a full scale deflection when the primary current is 900 Amps. Calculate: i) The maximum secondary current. ii) Secondary voltage at CT terminals when ammeter is removed.
Given: N_p = 1 turn, N_s = 180 turns, ammeter resistance R_A = 0.15 Ω, full-scale primary current I_p = 900 A, system voltage 400 V.
(i) Maximum secondary current
For a CT, ampere-turns balance (neglecting exciting current):
N_p · I_p = N_s · I_s
I_s = I_p × N_p/N_s
= 900 × 1/180
= 5 A
So the ammeter must be a 0–5 A meter giving full-scale at 5 A.
With the ammeter connected, the CT terminal voltage is only
V_s = I_s × R_A = 5 × 0.15 = 0.75 V
Primary drop = 0.75/180 = 0.00417 V ≈ 4.17 mV
(ii) Secondary voltage when the ammeter is removed
When the ammeter is removed, the secondary is open-circuited. There is no secondary m.m.f. to oppose the primary, so the CT behaves like a step-up voltage transformer of ratio 1 : 180 connected in the line. In the limit (core not saturated, no other limit), the voltage across the single-turn primary can rise up to the phase voltage of the system.
Assumption: 400 V is the line voltage of a 3-phase system, so phase voltage = 400/√3 = 230.94 V.
V_s(open) = V_p × N_s/N_p
= (400/√3) × 180
= 230.94 × 180
= 41 569 V ≈ 41.6 kV
(If 400 V were applied directly across the primary, V_s = 400 × 180 = 72 kV.)
Answer: (i) I_s(max) = 5 A (terminal voltage 0.75 V with ammeter). (ii) On open circuit the secondary voltage can rise to about 41.6 kV (theoretical upper limit; 72 kV if 400 V across primary).
In practice core saturation limits the r.m.s. value, but very high peak voltages still appear; this shows why a CT secondary must never be opened under load and must be short-circuited before removing the ammeter.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- CT secondary open and PT secondary short · Switchgear and Protection, chapter 2
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- Percentage differential relay: 125 MVA transformer · Switchgear and Protection, chapter 7
- Resistance switching numerical (220 kV, 600 Ω) · Switchgear and Protection, chapter 6 · asked 2×
- Resistance switching numerical (132 kV, 350 Ω) · Switchgear and Protection, chapter 6 · asked 2×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2
- Current transformer vs conventional; CT open · Electrical Machine, chapter 2