- 2073 Bhadra · 8 marks
Induction generator excitation capacitor value
Short answer
Drive rotor above synchronous speed to get negative slip and generate power. In isolated mode, a capacitor bank supplies lagging excitation. Determine capacitance: obtain magnetisation curve at desired voltage, find magnetising current Im; then Xc = Vph/Im; capacitance per phase (star) C = 1/(2πf Xc) (delta C = C/3).
Explain how an induction motor can be used as induction generator. Explain the procedure to determine the value of excitation capacitor required for voltage build up in the generator.
An induction motor works as an induction generator when its rotor is driven by a prime mover above synchronous speed (), so that slip is negative and mechanical power is converted into electrical power.
Motor to generator action
- With () the machine motors.
- Driven at (), the rotor cuts the field in the opposite sense; rotor emf, current and torque reverse. Air-gap power becomes negative: power flows from shaft to stator terminals.
- The machine still needs lagging reactive power to magnetize its core. On a grid it takes this from the grid. In isolated mode a 3-phase capacitor bank across the stator supplies it, and voltage builds up by self-excitation from residual magnetism.
Prime mover +------+
(N > Ns) ====| IG |===+======> Load
+------+ |
=== C per phase
Voltage settles where the magnetization curve meets the capacitor line .
Procedure to find the excitation capacitance
- Obtain the magnetization curve. Run the machine as a motor on no load (speed ) from a variable-voltage supply, or drive it at synchronous speed. Vary the applied phase voltage from about 120% of rated downwards and record the no-load (magnetizing) current . Plot against .
V | _.---- magnetization
| .-' curve
Vr|---.* <- required point
| /| capacitor line
| / | slope = Xc
|/__|_____________ Im
Im,r
- Choose the operating voltage (rated phase voltage) and read the corresponding magnetizing current from the curve.
- Capacitive reactance per phase — the capacitor line must pass through this point:
- Capacitance per phase (star-connected bank):
For a delta-connected bank (each capacitor at line voltage): . 5. Minimum capacitance: the capacitor line must be less steep than the linear (air-gap) part of the curve; otherwise voltage will not build up. The slope of the air-gap line gives and so . 6. Allowance for load: for a lagging load, extra capacitance is added to supply the load VAr, , so that voltage does not collapse. Also, because the slip is negative, the generated frequency is slightly below the speed-equivalent value , so the calculation should use this expected (slightly lower) operating frequency, not itself.
Example: 400 V, 50 Hz machine; at rated phase voltage 230.94 V the curve gives A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage build-up in isolated induction generator · Electrical Machines I, chapter 5
- Shunt generator voltage build-up, critical resistance and speed · Electrical Machines I, chapter 3 · asked 9×
- Starting shunt generator on no load and voltage build-up · Electrical Machines I, chapter 3
- Excitation capacitors in isolated and grid-connected induction generator · Electrical Machines I, chapter 5
- Shunt generator build-up conditions, critical speed and resistance · Electrical Machines I, chapter 3
- Induction motor as generator in grid-connected mode · Electrical Machines I, chapter 5 · asked 5×
- Induction generator and excitation capacitor · Electrical Machines, chapter 5
- Voltage build-up in induction generator · Electrical Machines, chapter 5
- Voltage build-up; series generator at no load · Electrical Machines, chapter 3
- Voltage build-up, critical resistance and speed · Electrical Machines, chapter 3 · asked 3×