- 2080 Chaitra · 8 marks
Pump-driven circulating pipe network
Short answer
Combine series–parallel pipe resistances to total R = 6184.1 s²/m⁵. Pump power P = γ R Q³ → Q = (500/(9810×6184.1))^(1/3) = 0.0202 m³/s (20.2 L/s).
A circulating pipe flow network as shown in Fig 1 is constructed for a cooling system in Tribhuwan University Main building. If a pump capacity of 500 watts is used at junction I, determine the maximum discharge that the pump can circulate in the system. [Figure: loop network A-B-C-D, then D to E (link DE), then E-F-G-H, then H to I (link HI), pump P at I, returning to A (link AI); discharge Q leaves/returns at the left]
| Link | f | L (m) | D (m) |
|---|---|---|---|
| AB | 0.06 | 10 | 0.1 |
| AC | 0.06 | 10 | 0.1 |
| BD | 0.06 | 10 | 0.1 |
| CD | 0.06 | 10 | 0.1 |
| DE | 0.05 | 15 | 0.2 |
| EF | 0.06 | 10 | 0.1 |
| EG | 0.06 | 10 | 0.1 |
| FH | 0.06 | 10 | 0.1 |
| GH | 0.06 | 10 | 0.1 |
| HI | 0.04 | 50 | 0.2 |
| AI | 0.04 | 50 | 0.2 |
Reading of the figure. The network is a closed circuit: A to D through a diamond (two parallel paths ABD and ACD), the link DE, E to H through a second diamond (paths EFH and EGH), then link HI, the pump at I, and link AI back to A. The same discharge passes through the whole circuit, and the pump head equals the total head loss. Only friction is considered, with .
Resistances (s²/m⁵)
- Each small link (, m, m):
- DE (, m, m):
- HI and AI (, m, m): each
Equivalent resistance of one diamond
Each path (e.g. A-B-D) has two links in series: . The two paths are identical, so the flow splits equally ( in each), and the head loss across the diamond is
Two diamonds in series: .
Total resistance of the circuit
Pump power and discharge
The pump supplies the head ; with power :
The head developed is m. The velocity in the 0.2 m links is m/s (and about 1.29 m/s in the 0.1 m links, where the flow is halved).
Answer: Maximum discharge l/s ( m³/s).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Pump power and pipe length with Colebrook · Hydraulics, chapter 2
- Flow distribution in five-pipe network · Hydraulics, chapter 3
- Three reservoirs with pump in pipe 2 · Hydraulics, chapter 3
- Critical flow at maximum discharge for given energy · Hydraulics, chapter 7
- Flow rate 2 s after pump failure · Hydraulics, chapter 4
- Duration of flow after pump stops · Hydraulics, chapter 4
- Service connection from main pipe to building · Water Supply Engineering, chapter 7 · asked 2×
- Centrifugal pump head, discharge and power · Fluid Machines, chapter 4
- Hardy-Cross network discharge AB, BC, AD, CD · Water Supply Engineering, chapter 7
- Cooling water and radiator air flow calculation · Internal Combustion Engines, chapter 7