- 2080 Chaitra · 6 marks
Capacitance depends on conductor size and spacing
Short answer
For a transposed three-phase line, capacitance per phase to neutral is C = 2*pi*epsilon0 / ln(Deq/r). This expression contains only the conductor radius r and equivalent spacing Deq, with epsilon0 constant. Hence conductor size and spacing are the primary factors; voltage, current and frequency do not appear.
Show that the capacitance per phase of a three-phase overhead transmission line is primarily determined by the conductor size and conductor spacings.
The capacitance to neutral of a transposed three-phase line is . It contains only the conductor radius r and the spacings (through ), apart from the constant . The derivation below shows this.
Potential difference between two conductors
For a long conductor with charge q C/m, the potential difference between two points at distances and is . For a group of conductors, using superposition:
Equilateral spacing D
Adding and using (balanced charges):
For a balanced system, . So
Unsymmetrical spacing (transposed)
Averaging over the three transposition sections gives the same form, with D replaced by the geometric mean spacing:
For bundled conductors, r is replaced by the bundle's self-GMD for capacitance, for example .
Conclusion
- is a constant (air). So C depends only on the ratio , that is, on conductor size and spacing.
- Larger r (or bundling) gives higher C. Larger spacing gives lower C. The dependence is logarithmic, so a big change in geometry causes only a modest change in C.
- Current, voltage and frequency do not appear in C. The earth's effect (images) is small for normal conductor heights and is neglected. That is why size and spacing are the primary factors.
Example: r = 1 cm and D = 4 m give nF/km. Doubling D to 8 m gives 8.32 nF/km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Single-phase line capacitance, 6 mm, 1.3 m · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Minimum conductor spacing for 230 kV corona limit · High Voltage Engineering, chapter 5 · asked 4×
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3