Complex power is S=P+jQ=VI*, with magnitude in VA. VI* gives positive Q for lagging inductive loads, matches the accepted convention that inductors absorb vars, and equals |I|^2Z. V*I would reverse the reactive sign and disagree with the standard power triangle.

What is complex power? Why is complex power taken as VI* rather than V*I in power systems? Explain.

Complex power is S=P+jQS = P + jQ, the phasor quantity whose real part is the active power (W), whose imaginary part is the reactive power (var) and whose magnitude is the apparent power (VA). It is defined as S=VI∗S = VI^*.

Why VI∗VI^*

Let V=∣V∣∠θvV = |V|\angle\theta_v and I=∣I∣∠θiI = |I|\angle\theta_i. The power-factor angle is ϕ=θv−θi\phi = \theta_v - \theta_i.

VI∗=∣V∣∣I∣∠(θv−θi)=∣V∣∣I∣cos⁡ϕ+j∣V∣∣I∣sin⁡ϕ=P+jQV∗I=∣V∣∣I∣∠(θi−θv)=∣V∣∣I∣cos⁡ϕ−j∣V∣∣I∣sin⁡ϕ=P−jQ\begin{aligned} VI^* &= |V||I|\angle(\theta_v - \theta_i) = |V||I|\cos\phi + j|V||I|\sin\phi = P + jQ\\ V^*I &= |V||I|\angle(\theta_i - \theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi = P - jQ \end{aligned}
  1. Both give the same P. Only the sign of Q differs.
  2. Sign agreement with the accepted convention. With VI∗VI^*, a lagging (inductive) load (θi<θv\theta_i < \theta_v, ϕ>0\phi > 0) gives Q>0Q > 0. Inductive loads "absorb" vars and capacitors "supply" vars. This is the convention adopted by IEEE/IEC and used in load-flow studies, generator capability charts and var meters. With V∗IV^*I, an inductive load would show negative Q, which conflicts with the convention.
  3. Consistency with impedance. With S=VI∗=∣I∣2Z=∣I∣2(R+jX)S = VI^* = |I|^2Z = |I|^2(R + jX), inductive reactance (+X) gives +Q. The power triangle is then the impedance triangle scaled by ∣I∣2|I|^2. With V∗IV^*I the triangle would be the mirror image of the impedance triangle.
  4. Independence from reference. Taking the conjugate removes the absolute phase angles and keeps only the difference θv−θi\theta_v - \theta_i. So S does not depend on which phasor is chosen as reference. (VIVI without a conjugate would give the angle θv+θi\theta_v + \theta_i, which changes with the reference and has no meaning.)
 Im(Q)
  ^        S = VI*
  |      /
  |    /  Q = |V||I| sin(phi) > 0
  |  / phi    (lagging load)
  +----------> Re (P)

Example: V=100∠0∘V = 100\angle0^\circ V and I=10∠−30∘I = 10\angle-30^\circ A (lagging). Then VI∗=866+j500VI^* = 866 + j500 VA, which is correct: the load absorbs 500 var. But V∗I=866−j500V^*I = 866 - j500 VA would wrongly suggest that the inductive load supplies vars.