Generator and load complex power conventions
Short answer
Complex power is S=VI*; for a generator current leaves the terminal so S is delivered, for a load current enters so S is absorbed. If the conjugate is not used, V*I gives P but reverses the sign of Q, while VI depends on the chosen reference angle and is physically meaningless.
How are generator and load complex powers expressed? What will happen if the convention of taking the conjugate of current is not followed? Explain with necessary derivation.
Generator and load complex power
Complex power is always written as . What it means depends on the assumed current direction.
- Generator (source) convention: the current leaves the + terminal. is the power delivered. For an over-excited generator supplying a lagging load, and .
- Load convention: the current enters the + terminal. is the power absorbed. For an inductive load : with .
At any bus, the net injected power is . This is the form used in load-flow studies.
If the conjugate is not taken
Let , and .
Case 1:
P is correct, but the sign of Q is reversed. An inductive (lagging) load would show negative Q, as if it were supplying vars like a capacitor. Generators and loads would then disagree with the standard convention used in meters, capability charts and load-flow programs. The power triangle would also become the mirror image of the impedance triangle ().
Case 2: (no conjugate at all)
The angle now depends on the sum of the phase angles. If the reference is changed by , then becomes . So P and Q would change just because a different phasor was chosen as reference, which is physically meaningless. Taking the conjugate makes S depend only on the difference , which is independent of the reference.
Example: V and A (lagging by 30°).
- VA. Correct: an inductive load absorbs 500 var.
- VA. Wrong sign of Q.
- here, but with V as reference (, ) it becomes . The result changes with the reference.
So the conjugate of current must be taken to get a unique, reference-independent S with the standard sign of Q.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Complex power and sign conventions · Power System Analysis I, chapter 3
- Derivation and phasor diagram of complex power · Power System Analysis I, chapter 3
- Compensation does not reduce load reactive demand · Power System Analysis I, chapter 6
- Complex power and its significance · Power System Analysis I, chapter 3 · asked 2×
- Complex power and why VI* rather than V*I · Power System Analysis I, chapter 3
- Complex power, impedance and power triangles · Power System Analysis I, chapter 3
- DT complex exponential periodic if rational · Signals and Systems, chapter 1
- Power to 10 Ω load from shunt generator · Electrical Machines I, chapter 3
- Wave-wound shunt generator, power absorbed by load · Electrical Machines, chapter 3
- UH derivation from complex storms · Engineering Hydrology, chapter 5