- 2071 Magh · 6 marks
Derivation and phasor diagram of complex power
Short answer
Complex power S = VI* = P + jQ, with P = |V||I|cosφ (real power, W) and Q = |V||I|sinφ (reactive power, var). P does useful work; Q is energy exchanged with magnetic/electric fields and sets voltage levels.
Starting from voltage and current phasors, derive the expression for complex power. Construct the phasor diagram of complex power and explain the significance of the components.
Complex power S is the phasor product of the voltage and the conjugate of the current. Its real part is the average (active) power and its imaginary part is the reactive power.
Derivation
Let the instantaneous voltage and current be
The instantaneous power is
Here , and .
- The first term has average . This is the active power.
- The second term has zero average and peak . This is the reactive power.
In phasor form, and . Then
For a load : .
Phasor diagram and power triangle
V reference (lagging load) Power triangle
---------------> V /|
\ phi S / | Q = |V||I|sin(phi)
\ / |
\ I (lags V) / phi |
v +-------+
P = |V||I|cos(phi)
Multiplying V by the conjugate of I turns the V–I phasor diagram into a right-angled triangle. The hypotenuse is , the base is P, the height is Q, and the angle is .
Significance of the components
| Component | Unit | Meaning |
|---|---|---|
| P (real part) | W | Average power converted to useful work and losses. It is what energy meters record. |
| Q (imaginary part) | var | Power exchanged back and forth with magnetic and electric fields. It is needed for magnetising and sets the voltage levels, but does no net work. |
| VA | Sets the current and the rating of generators, transformers and cables | |
| , | — | Power factor: the share of S that is useful power |
- Q > 0 means a lagging (inductive) load and Q < 0 a leading (capacitive) load.
- A low power factor means more current for the same P. This causes more loss, more voltage drop and larger equipment. So utilities add capacitors to reduce Q.
Example: V and A give VA, with pf 0.8 lagging.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-π derivation, losses and UPF phasor diagram · Power System Analysis I, chapter 5
- Nominal-T derivation, phasor, losses, regulation · Power System Analysis I, chapter 5
- Complex power and its significance · Power System Analysis I, chapter 3 · asked 2×
- Receiving end complex power and power circle · Power System Analysis I, chapter 6
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Generator and load complex power conventions · Power System Analysis I, chapter 3
- Significance of components; phasor voltages · Power System Analysis II, chapter 4
- Symmetrical components and complex power · Power System Analysis II, chapter 4
- Importance and derivation of current components · Power System Analysis II, chapter 4
- Reactive power and power phasor diagram · Basic Electrical Engineering, chapter 7