- 2068 Bhadra · 5 marks
5-disc string at 66 kV: nearest and farthest disc
Short answer
For a 66 kV line (phase voltage 38.1 kV) and five discs with capacitance ratio 0.1, the disc nearest the conductor carries 11.39 kV (29.9% of phase voltage) and the farthest disc carries 5.28 kV (13.9%). The nearest disc is stressed more than twice the farthest.
There are five discs in a string of insulators used in a 3-phase, 66 kV overhead transmission line. Compute the voltage distribution at the nearest and farthest disc from the phase conductor.
The ratio of shunt to self-capacitance is not given. Assume the usual value (shunt capacitance 10 % of disc capacitance).
Data
- Phase voltage: kV
- Discs numbered 1 (farthest from the conductor, at the tower) to 5 (nearest the conductor)
Relations
| Disc | Voltage (kV) | % of |
|---|---|---|
| 1 (farthest, at tower) | 5.279 | 13.85 % |
| 2 | 5.807 | 15.24 % |
| 3 | 6.916 | 18.15 % |
| 4 | 8.716 | 22.87 % |
| 5 (nearest conductor) | 11.388 | 29.88 % |
String efficiency:
Answer (with ): The disc nearest the conductor carries 11.39 kV (29.9 % of ), and the farthest disc carries 5.28 kV (13.9 % of ). The nearest disc is stressed more than twice as much as the farthest one.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage distribution on 4-disc string at 33 kV · Power System Analysis I, chapter 2
- String of 4 insulators at 66 kV, ratio 10 · Power System Analysis I, chapter 2
- String efficiency: 66 kV, 4 discs, 10% · Power System Analysis I, chapter 2 · asked 2×
- 5-disc string at 66 kV, ratios 5 and 6 · Power System Analysis I, chapter 2
- Line voltage from disc voltages of 4-disc string · Power System Analysis I, chapter 2
- Maximum voltage of 3-disc string, 17.5 kV per unit · Power System Analysis I, chapter 2
- Number of insulator discs for 220 kV line · Transmission and Distribution System Design, chapter 3
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Voltage, circuits, discs: 200 MW, 160 km · Transmission and Distribution System Design, chapter 2
- Voltage, circuits and discs for 260 MW grid link · Transmission and Distribution System Design, chapter 2