Need for different voltage levels

Short answer

Generators are limited to 11–25 kV, bulk transmission needs high voltage (132–400 kV) to reduce I^2 R loss (loss ∝ 1/V^2), and consumers require low 400/230 V for safety. Transformers allow economical voltage changes between these levels.

Why are different voltage levels required in an interconnected power system? Explain with a neat sketch of an interconnected power system showing different voltage levels.

Different voltage levels are used because no single voltage is best for every part of the system: generators are limited to a moderate voltage, bulk power must be sent far at very high voltage to keep losses low, and consumers need a low, safe voltage.

Reasons

  1. Generation limit: Generator insulation in the stator slots limits the voltage to about 11–25 kV (Nepal: 6.6/11 kV).
  2. Low transmission loss: For a given power, I=P/(3Vcos⁡ϕ)I = P/(\sqrt3 V\cos\phi), so loss 3I2R∝1/V23I^2R \propto 1/V^2. Raising voltage from 11 kV to 132 kV cuts the loss by (132/11)2=144(132/11)^2 = 144 times.
  3. Less conductor material: Conductor volume for the same loss is ∝1/V2\propto 1/V^2, so high voltage saves copper/aluminium.
  4. Better regulation and capacity: % voltage drop ∝1/V2\propto 1/V^2; power capacity of a line ∝V2\propto V^2 (e.g. Pmax=VsVr/XP_{max} = V_sV_r/X).
  5. Distance and power: Longer lines and larger blocks of power need higher voltage (400 kV for hundreds of km, 33 kV for tens of km).
  6. Safety and cost at the user end: Very high voltage needs large clearances and costly insulation; so in towns it is stepped down to 11 kV and finally 400/230 V for safe use.

Interconnected system with voltage levels

 [G] 11 kV       Step-up       Transmission
  |---->[11/220 kV]====== 220/400 kV ======+
                                            |
 [G] 11 kV                          [220/132 kV]
  |---->[11/132 kV]====== 132 kV ====== Grid S/S
                                            |
                              Sub-transmission 66/33 kV
                                            |
                                    [33/11 kV] S/S
                                            |
                              Primary distribution 11 kV
                                            |
                                    [11/0.4 kV] DT
                                            |
                         Secondary 400/230 V consumers
PartTypical voltage (Nepal)
Generation6.6, 11 kV
Transmission400, 220, 132 kV
Sub-transmission66, 33 kV
Primary distribution11 kV
Secondary distribution400/230 V

Transformers make these levels possible economically; this is one of the main reasons AC is used for power systems.