Interconnected system load-frequency and Q-V control
Short answer
Interconnection improves reliability, reserve sharing, load diversity, and enables economic dispatch, but raises fault levels and risk of cascading outages. Load/frequency is controlled by the P-f loop: a governor reduces speed error and AGC adjusts setpoint using ACE to restore nominal frequency. Reactive/voltage control uses the Q-V loop: an AVR and exciter adjust field current to regulate terminal voltage.
What are the advantages and disadvantages of interconnected power system? With the schematic diagram, explain how load/frequency and reactive power/voltage are controlled in the power system.
An interconnected power system links many generating stations and areas by tie-lines so that they operate in synchronism. Its two main control loops are the load-frequency (P–f) loop and the reactive power–voltage (Q–V) loop.
Advantages
- Higher reliability; a failed unit's load is picked up by others.
- Less reserve capacity, as reserve is shared.
- Load diversity gives lower installed capacity and better load factor.
- Economic dispatch of the cheapest units; power exchange between areas.
- Larger combined inertia gives better frequency regulation.
Disadvantages
- Higher fault levels, so higher-rated breakers are needed.
- A fault can cascade and black out a large area.
- Stability and protection coordination become more complex.
- Costly tie-lines and communication/SCADA systems.
Control schematic
P-f loop (frequency)
Speed changer (AGC set point)
|
Speed/frequency -> [Governor] -> [Valve] -> [Turbine] --Pm--> [Generator]
^ |
+------------- speed (frequency) feedback ----------------+
Q-V loop (voltage)
Vref --> (+/-) --> [AVR] --> [Exciter] --If--> [Generator field]
^ |
+-------- measured terminal voltage V -----+
Load / frequency control (P–f loop)
- A load increase makes . The deficit is taken from rotor kinetic energy, so speed and frequency fall.
- The speed governor senses and opens the steam/water valve, increasing . With droop , the steady-state change is ; a small error remains.
- Automatic Generation Control (AGC) adds an integral of the area control error to the speed-changer set point, bringing and tie-line deviation to zero.
Reactive power / voltage control (Q–V loop)
- The terminal voltage is measured, rectified and compared with .
- The error is amplified by the AVR and drives the exciter, which changes the field current and hence the internal emf .
- Higher makes the generator supply more Q and raises the bus voltage; lower absorbs Q and lowers it.
- In the network, voltage is also held by shunt capacitors/reactors, synchronous condensers, SVC/STATCOM and tap-changing transformers.
Because , P depends mainly on and Q mainly on , so the two loops can be designed and operated independently.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Real power/frequency control in interconnected system · Power System Analysis II, chapter 1
- Role of interconnection and reactive power control · Power System Analysis II, chapter 1
- Reactive power and voltage balance · Power System Analysis II, chapter 1
- Generator reactive power at constant terminal voltage · Power System Analysis II, chapter 1
- Advantages of interconnected power system · Power System Analysis II, chapter 1 · asked 3×
- Effects of real and reactive power mismatch · Power System Analysis II, chapter 1 · asked 4×
- Reactive power proportional to voltage drop · Power System Analysis I, chapter 6
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Reactive power and power phasor diagram · Basic Electrical Engineering, chapter 7
- Interconnected power system and advantages · Power System Analysis I, chapter 1