Short answer

Interconnection improves reliability, reserve sharing, load diversity, and enables economic dispatch, but raises fault levels and risk of cascading outages. Load/frequency is controlled by the P-f loop: a governor reduces speed error and AGC adjusts setpoint using ACE to restore nominal frequency. Reactive/voltage control uses the Q-V loop: an AVR and exciter adjust field current to regulate terminal voltage.

What are the advantages and disadvantages of interconnected power system? With the schematic diagram, explain how load/frequency and reactive power/voltage are controlled in the power system.

An interconnected power system links many generating stations and areas by tie-lines so that they operate in synchronism. Its two main control loops are the load-frequency (P–f) loop and the reactive power–voltage (Q–V) loop.

Advantages

  • Higher reliability; a failed unit's load is picked up by others.
  • Less reserve capacity, as reserve is shared.
  • Load diversity gives lower installed capacity and better load factor.
  • Economic dispatch of the cheapest units; power exchange between areas.
  • Larger combined inertia gives better frequency regulation.

Disadvantages

  • Higher fault levels, so higher-rated breakers are needed.
  • A fault can cascade and black out a large area.
  • Stability and protection coordination become more complex.
  • Costly tie-lines and communication/SCADA systems.

Control schematic

 P-f loop (frequency)
                   Speed changer (AGC set point)
                            |
 Speed/frequency -> [Governor] -> [Valve] -> [Turbine] --Pm--> [Generator]
        ^                                                          |
        +------------- speed (frequency) feedback ----------------+

 Q-V loop (voltage)
 Vref --> (+/-) --> [AVR] --> [Exciter] --If--> [Generator field]
            ^                                          |
            +-------- measured terminal voltage V -----+

Load / frequency control (P–f loop)

  1. A load increase makes Pe>PmP_e > P_m. The deficit is taken from rotor kinetic energy, so speed and frequency fall.
  2. The speed governor senses Δf\Delta f and opens the steam/water valve, increasing PmP_m. With droop RR, the steady-state change is Δf=−ΔPL/(∑1/R+D)\Delta f = -\Delta P_L / (\sum 1/R + D); a small error remains.
  3. Automatic Generation Control (AGC) adds an integral of the area control error ACE=ΔPtie+BΔfACE = \Delta P_{tie} + B\Delta f to the speed-changer set point, bringing Δf\Delta f and tie-line deviation to zero.

Reactive power / voltage control (Q–V loop)

  1. The terminal voltage is measured, rectified and compared with VrefV_{ref}.
  2. The error is amplified by the AVR and drives the exciter, which changes the field current IfI_f and hence the internal emf EfE_f.
  3. Higher EfE_f makes the generator supply more Q and raises the bus voltage; lower EfE_f absorbs Q and lowers it.
  4. In the network, voltage is also held by shunt capacitors/reactors, synchronous condensers, SVC/STATCOM and tap-changing transformers.

Because X≫RX \gg R, P depends mainly on δ\delta and Q mainly on ∣V∣|V|, so the two loops can be designed and operated independently.

✓ Answer checked by Claude Sonnet 5.5