Shunt compensation: need and two methods

Short answer

Shunt compensation is necessary for voltage control, loss reduction, better power factor, higher transfer capacity, and voltage stability. Two methods: (1) Fixed/switched shunt capacitors supply lagging Mvar at heavy load, reactors absorb charging Mvar at light load. (2) SVCs combine thyristor-controlled reactors and switched capacitors for fast continuous reactive power control.

Why is shunt compensation necessary in a transmission line? Explain any two methods of shunt compensation applied in transmission systems.

Shunt compensation means connecting reactive-power devices (capacitors, reactors, or controlled devices) in parallel with the line or at the buses, to supply or absorb reactive power.

Why shunt compensation is necessary

  • Voltage control at heavy load: large lagging loads draw reactive current, which causes a large voltage drop (ΔV≈QX/V\Delta V \approx QX/V). Shunt capacitors supply this Q locally and hold up the voltage.
  • Voltage control at light load: below SIL the line's charging Mvar exceeds its inductive absorption, so voltage rises (Ferranti effect). Shunt reactors absorb this excess.
  • Reduced losses and current: supplying Q near the load reduces line current, I2RI^2R loss and heating.
  • Better power factor and released capacity of generators, transformers and lines.
  • Higher power transfer and voltage stability: holding the mid-point or receiving voltage up raises the transfer limit P=VSVRXsin⁡δP = \frac{V_SV_R}{X}\sin\delta and helps prevent voltage collapse.

Method 1: Shunt capacitors and shunt reactors (fixed or switched)

   Bus  ---+-------------+----- line
           |             |
          === C        (((L)))
           |             |
          ---           ---
       capacitor      reactor
  • Shunt capacitor banks at substations and load centres supply lagging Mvar; they are switched in steps as load rises. They are cheap, low-loss and simple.
  • Shunt reactors at the ends of long EHV lines absorb charging Mvar at light load and limit the Ferranti rise and switching overvoltages.
  • Limitation: control is in steps, and capacitor output falls as V2V^2, just when support is most needed.

Method 2: Static VAR compensator (SVC)

   Bus ----+-----------+-----------+
           |           |           |
         [TCR]       [TSC]       [Filter /
       thyristor-  thyristor-    fixed C]
       controlled   switched
        reactor    capacitor
  • A thyristor-controlled reactor (TCR) varies the absorbed Q continuously by controlling the firing angle.
  • Thyristor-switched capacitors (TSC) or fixed capacitors provide the capacitive range.
  • Together they act as a fast, continuously variable susceptance, from capacitive to inductive, responding within a few cycles.
  • Used for dynamic voltage control, damping oscillations and improving transient stability.

Other shunt methods: synchronous condensers (over- or under-excited synchronous machines giving smooth Q control) and STATCOM (a voltage-source converter; it is faster than an SVC and keeps up its reactive current output at low voltage).