Interconnection advantages and real power-frequency balance

Short answer

Interconnected systems offer higher reliability, reduced reserve, economic dispatch, load diversity, larger efficient units, and better frequency stability. Real power–frequency balance: a load change causes frequency deviation; primary governor control (droop) shares the mismatch among units, then secondary AGC resets frequency to nominal and restores tie-line flows.

List out the advantages of interconnected power system over isolated power system. Explain how real power and frequency balance is maintained in an interconnected power system.

An interconnected power system is one in which several generating stations and areas are tied together by transmission lines (tie-lines), so that they all run in synchronism and share load. Compared with isolated systems, it is cheaper and more reliable, and its frequency is held by keeping total generation equal to total load.

Advantages over an isolated system

  1. Better reliability: if a unit or plant trips, the others pick up its load through tie-lines, so supply continues.
  2. Less reserve capacity needed: spinning and standby reserve is shared by all areas, so each area keeps less idle capacity.
  3. Economic operation: the cheapest units (e.g. run-of-river hydro in Nepal) are loaded first and power is sent to where it is needed (economic dispatch across areas).
  4. Use of diversity: peak demands of different areas occur at different times, so the total installed capacity required is lower; load factor and plant factor improve.
  5. Larger, more efficient units can be installed because the large system can absorb them.
  6. Better use of energy resources: surplus hydro energy in the wet season can be exported (e.g. Nepal–India power trade) and imported in the dry season.
  7. Better frequency stability: the combined inertia is large, so a load change produces only a small frequency change.
  8. Easier maintenance scheduling, since units can be taken out while others supply load.

Real power–frequency balance

At steady state, total mechanical input equals total load plus losses, and frequency is constant. When load changes by ΔPL\Delta P_L:

  1. Inertia response: the deficit is supplied from the kinetic energy of all rotors, so speed and frequency fall (swing equation 2Hωsd2δdt2=Pm−Pe\frac{2H}{\omega_s}\frac{d^2\delta}{dt^2} = P_m - P_e).
  2. Primary (governor) control: each governor with droop RR raises mechanical power by ΔPm,i=−Δf/Ri\Delta P_{m,i} = -\Delta f / R_i. Load also falls a little with frequency (damping DD). Steady-state deviation:
Δf=−ΔPL∑i1Ri+D\Delta f = \frac{-\Delta P_L}{\sum_i \dfrac{1}{R_i} + D}

All interconnected units share the load change in inverse proportion to their droop. 3. Secondary control (AGC): in each area an integral controller acts on the Area Control Error

ACE=ΔPtie+B ΔfACE = \Delta P_{tie} + B\,\Delta f

and moves the speed-changer set points until ACE=0ACE = 0. Then frequency returns to the nominal value (50 Hz in Nepal) and tie-line flows return to schedule, so each area finally supplies its own load change. 4. Tertiary control: economic dispatch resets the unit outputs for minimum cost.

 Load change -> f falls -> Governor opens valve
      ^                         |
      |                         v
   P_gen = P_load  <-  AGC resets speed changer